Bard 357-93-E manual Unit Service Access Overview

Models: 357-93-E

1 12
Download 12 pages 51.81 Kb
Page 9
Image 9
Unit Service Access Overview

Indoor Blower Performance - CFM at 230 or 460 Volts

 

WL18

 

WL30

 

WL42

 

 

ESP

WL24

 

 

WL60, WL70

 

WL37

 

WL48

in

WL25

 

 

 

 

 

 

 

 

 

 

H2O

Dry/Wet Coil

High Speed

Low Speed

High Speed

Low Speed

High Speed

Low Speed

 

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

 

 

0

1020/975

1395/1315

950/935

1885/1800

1650/1600

2200/2000

1600/1450

 

 

 

 

 

 

 

 

.1

960/905

1340/1270

930/915

1770/1665

1550/1500

2100/1900

1525/1375

 

 

 

 

 

 

 

 

.2

865/800

1285/1190

910/885

1635/1550

1450/1400

2000/1800

-/-

 

 

 

 

 

 

 

 

.3

820/735

1205/1100

855/830

1500/1400

1350/1300

1875/1700

-/-

 

 

 

 

 

 

 

 

.4

735/650

1110/1000

800/755

1370/1285

1300/1175

1775/1600

-/-

 

 

 

 

 

 

 

 

.5

615/535

1005/870

-/-

1250/1150

-/-

1650/1475

-/-

 

 

 

 

 

 

 

 

Above data is with 1" standard disposable filter and 1" washable filter.

For optional 2" pleated filter - reduce ESP by .15 in.

See installation instructions for maximum ESP information on various KW application.

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model

Nominal

 

At 240V (1)

 

 

At 208V (1)

 

 

At 480V (2)

 

 

At 460V (2)

 

KW

Kw

1-Ph Amps

3-Ph Amps

Btuh

Kw

1-Ph Amps

3-Ph Amps

Btuh

Kw

3-Ph Amps

Btuh

Kw

3-Ph Amps

Btuh

 

5.0

5.0

20.8

 

17,065

3.75

18.0

 

12,799

 

 

 

 

 

 

6.0

6.0

 

14.4

20,478

4.50

 

12.5

15,359

6.0

7.2

20,478

5.52

6.9

18,840

8.0

8.0

33.3

 

27,304

6.00

28.8

 

20,478

 

 

 

 

 

 

9.0

9.0

 

21.7

30,717

6.75

 

18.7

23,038

9.0

10.8

30,717

8.28

10.4

28,260

10.0

10.0

41.7

 

34,130

7.50

36.1

 

25,598

 

 

 

 

 

 

15.0

15.0

62.5

36.1

51,195

11.25

54.1

31.2

38,396

15.0

18.0

51,195

13.80

17.3

47,099

(1)These electric heaters are available in 230/208V units only.

(2)These electric heaters are available in 480V units only.

Unit Service Access Overview

ELECTRIC HEAT ACCESS PANEL

ELECTRICAL CONTROL ACCESS PANEL

COMPRESSOR ACCESS

￿ 15"

￿

￿

￿

Model WL with Left Side

Control Panel

￿

￿

ELECTRIC HEAT

ACCESS PANEL

 

ELECTRICAL

￿ CONTROL ACCESS PANEL

COMPRESSOR

￿ ACCESS

Model WA with Right Side

Control Panel

NOTE: A 15-inch clearance between units is required when model WL and model WA are mounted side by side. This provides for proper service access to condenser fan and motor shroud assembly and adequate condenser air flow.

Form No.

S3279-206

Supersedes

S3279-106

Page

9 of 12

Page 9
Image 9
Bard 357-93-E manual Unit Service Access Overview