Bard 8403-060 997-060180-4d, II. PROGRAMMING YOUR CONTROLLER programmable models only, Every Day

Models: 8403-060

1 8
Download 8 pages 31.5 Kb
Page 3
Image 3
II.PROGRAMMING YOUR CONTROLLER (programmable
WARNING: Before installing controller, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
SECURITY LOCKOUT
ENTER PIN NUMBER
0 0 0 0
PREVIOUS
SECURITY LOCKOUT
TEMP ADJUST ONLY
TOTAL KEYPAD LOCKOUT
PREVIOUS
CHANGE SETTING
∇∆
PREVIOUS
CHANGE SETTING
∇∆
FAN ON TIME
5
MINUTES
1. If the FAN hasn’t been on for an hour, the fan will start cycling based on these times. Default is OFF. The first screen is the amount of time you want the fan to be energized. Ranges are OFF, or 5-20 minutes in 5 minute increments.
2. After entering this time and pressing the center button ■, the next screen is the amount of time the fan is OFF. Ranges are 0 minutes, or 5-40 minutes in 5 minute increments.
3. After entering this time and pressing the center button ■ you will be returned to the Setting Menu screen.
4. Fan ON and OFF cycles will continue until the
fan has been energized by a call for heating or cooling.
SAVE
PREVIOUS
IDLE 10:00P 62
82 AUTO
SERVICE INFORMATION
MENU → SETTINGS → SERVICE INFORMATION
These screens help an installer or contractor to have a good understanding of what problems might be occurring before arriving for service. The options are TEMPERATURE and INPUTS. The TEMPERATURE will display the internal sensor temperature, the Room temperature and the reading from the Outdoor thermistor. INPUTS displays the status of the controller control lines. (W1/E, W2, Y1, Y2, G, O/B, A, Y0/D)
INTERMITTENT FAN
NO HEAT OR COOL CALL
FAN OFF TIME
10
MINUTES
INTERMITTENT FAN
NO HEAT OR COOL CALL
INTERMITTENT FAN
MENU → SETTINGS → INTERMITTENT FAN
Temperature conditions can vary widely between the controller location and extremities of the space the controller serves. This air stratification problem can be especially pronounced during mild outdoor conditions when long periods elapse between space conditioning demands from the controller. This intermittent fan operation can also improve the performance of air cleaning or special filtration systems that locate the cleaning or filtration media at the return air side of the fan.
8. If you selected TEMP ADJUST ONLY, you will only be able to adjust the set point temperature. Any other operation will require the pin number to unlock the controller.
9. Once unlocked, you’ll have to set a pin number again to lockout the thermostat again.
AUTO CHANGEOVER
With auto changeover, the controller automatically switches itself from heating to cooling, or vise versa, based on the setpoints. When setting up the controller you have to enter both a cooling setpoint and a heating setpoint. The controller will also prevent the user from setting the cooling setpoint lower than the heating setpoint. Mode is set to AUTO for this operation to work.
MENU → SETTINGS → AUTO CHANGEOVER
Auto Changeover Time - This setting sets the minimum off time before the controller can change from one mode to another. Default is 10 minutes. Range is from 5-120 minutes in 5 minute increments. Pressing the Right and Left buttons together for 3 seconds will over ride this delay for one cycle.
Auto or Manual Change – Default is AUTO. If MANUAL is chosen, you will need to change from heating to cooling or vise versa. When MANUAL is set, AUTO is removed from the MODE screen as a choice.

997-060180-4d

the MODE to OFF, and then back to the operating mode, typically AUTO.

4.If step 3 is not done within 10-minutes the display will automatically return to the SERVICE NEEDED screen in RED.

II.PROGRAMMING YOUR CONTROLLER (programmable

models only)

PROGRAMMING A DAY OR A SERIES OF DAYS

After selecting the programming screen, you have the option of programming everyday, weekdays, weekends, or individual days. Once you’ve selected a certain day to program, a screen appears that allows you to set the time, heat setting, cool setting, and fan operation for each event.

1.From the Main Menu, scroll to MENU and press the center button ■ on the keypad.

2.

Select PROGRAM

 

 

PROGRAM MENU

 

 

 

 

 

 

 

 

 

3.

Select PROGRAMMABLE.

 

SAVE

 

 

MONDAY

 

TUESDAY

 

 

4. You can program each day differently

 

 

 

WEDNESDAY

 

THURSDAY

 

 

 

by going through each day and

 

 

 

FRIDAY

 

 

SATURDAY

 

 

 

 

 

 

SUNDAY

 

personalizing them. Or, you can program

 

 

 

 

 

 

 

 

EVERY DAY

 

 

 

 

WEEKDAYS

 

everyday the same by scrolling to

 

WEEKENDS

 

 

 

 

 

SELECT OPTION ∇∆ COPY

 

EVERYDAY. Or, you can program

PREVIOUS

 

 

 

the weekdays or weekends the same by

 

 

 

 

 

 

 

 

 

selecting the appropriate menu item.

EVERY DAY

 

 

5. To program everyday the same, select

 

 

ACTIVE HEAT

COOL

FAN

 

EVERYDAY and then press the center

 

 

6:00A

 

70

78

AUTO

 

 

 

 

 

 

 

 

button ■.

6.Using the right arrow button ►, highlight

the WAKE time, and change to desired time by using the up and down arrow ▲▼ buttons. Move to the next entry by using the right arrow button ►. To change the HEAT set point, use the up and down arrows.

Continue this process

until all settings are to your liking.

7.The FAN setting will only be used if the Fan is set to

PROGRAMMED.

If the Events are set to 2 per day in the

Business mode, the fan will be

 

ON and the Ventilation output

(A) will be ON when the time is in the

OCCUPIED (Active) state. In

the Unoccupied (IDLE) state, the fan will

run in the operating

mode set by the program.

 

 

8.To save these setting, scroll to SAVE, and press the center button ■.

COPYING A PROGRAM FROM ONE DAY TO ANOTHER

In the PROGRAM menu, there is an option to COPY. The option can be used to copy the program from one day to another day. After COPY is selected, the controller will prompt you for which day to copy from. Next, it will prompt you for which day to copy the program to. After these selections, it will then confirm what is being copied to where. At this point you have the option of canceling the copy process, by pressing

to return to the copy menu, or saving what you have by pressing the center button ■. The SAVED screen will appear returning you to the copy menu. Pressing ◄ will return you to the PROGRAM menu. Pressing ◄ again will return you to the MAIN MENU.

SECURITY LOCKOUT

This controller has the option to set security features to lockout everything but the adjustment of the temperature or a total keypad lockout.

1.From the Main Menu, scroll to MENU and press the center button ■ on the keypad.

2. Select SECURITY LOCKOUT.

SELECT OPTION ∇∆

3.Select whether you want to lockout everything

but TEMP ADJUST ONLY or TOTAL KEYPAD LOCKOUT.

4. Either selection will bring you to the Enter Pin Number screen.

5.Using the up and down arrows ▲▼, select a

pin number to lock out the thermostat. The

CHANGE NUMBER ∇∆

PREVIOUS

right arrow ► moves you to the next pin digit.

 

6.Once you’ve entered the 4-digit pin number, press the center button ■ to save the pin. The screen will display LOCKED and return to the main Screen.

7.Once you return to the Main Screen, in the upper left of the screen will alternate between LOCKED and the date and time.

3

Page 3
Image 3
Bard 8403-060 user manual 997-060180-4d, II. PROGRAMMING YOUR CONTROLLER programmable models only, Every Day