997-060180-4d
INSTALLER
INFORMATION / ADVANCED FEATURES
SAFETY CONSIDERATIONS
Improper wiring or installation may damage controller. Wiring must conform to local and national electrical codes
INTRODUCTION
The controller is a wall mounted, 24VAC
INSTALLATION CONSIDERATIONS
The controller requires no batteries. The controller is not a power stealing device and MUST have both R and C connected.
INSTALLATION
IV. CONTROLLER LOCATION
Controller should be mounted:
-Approximately 5 ft. (1.5m) from floor.
-Close to or in a frequently used room, preferably on an inside partitioning wall.
-On a section of wall without pipes or duct work.
Controller should NOT be mounted:
-Close to a window, on an outside wall, or next to a door leading to the outside.
-Exposed to direct light and heat from a lamp, sun, fireplace, or other
-Close to or in direct airflow from supply registers and
-In areas with poor air circulation, such as behind a door or in an alcove.
V. INSTALL CONTROLLER
1.Turn off all power to unit.
2.If an existing thermostat is being replaced:
A.Remove existing thermostat from wall.
B.Disconnect wires from existing thermostat, one at a time. Be careful not to allow wires to fall back into the wall.
C.As each wire is disconnected, record wire color and terminal marking.
D.Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be disposed of properly.
3.Separate the front and back pieces of plastic.
4.Route thermostat wires through hole in back piece of plastic. Level plastic against wall (for aesthetic value only - thermostat need not be leveled for proper operation) and mark wall through 2 mounting holes.
5.Drill two
6.Secure back plastic to wall with 2 anchors and screws provided making sure all wires extend through hole in plastic.
7.Use minimum of
8.Push any excess wire back into wall. Excess wire inside the controller plastic case can interfere with proper air flow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can affect operation.
9.Snap front and back pieces of plastic together.
10.Turn on power to the unit.
VI. INSTALLER SETTINGS
NOTE: These options are intended to be used by the installer. End users are not advised to change or modify any of these settings. Doing so may make your equipment stop working properly and/or may void the warranty of the controller as well as the equipment hooked up to the controller. To access the installer setting menu, the mode must be set to OFF. Then, press both the up and down arrows keys at the same time for at least 5 seconds to enter the installer screen.
MODEL CONFIGURATION
Options to select from:
HEAT COOL/HEAT PUMP,
SINGLE STAGE/MULTI STAGE,
ECONOMIZER/NO ECONOMIZER
CS2000A INSTALLED..YES OR NO
PROGRAMMABLE/NONPROGRAMMABLE
BOLD items are default
NOTE: - If CS2000A is installed, the controller will inhibit all outputs except the Y0/D when there is no 24Vac applied to the L input on the thermostat. When the CS2000A is not installed, the L input is the Lock out signal from the heat pump.
ACCESSORIES
Each of these options has settings for Cumulative Run Time and Calendar Time. Messages will flash at the top of the Main screen when these events are met to alert the owner that it is time service these options.
Air Filter - Cumulative Run Time default is 1000 hours and Calendar Time is 3 months. Values can range from
Humidifier - Cumulative Run Time default is 0 hours (OFF) and Calendar Time is OFF. Values can range from
UV Lamp - Cumulative Run Time default is 0 hours (OFF) and Calendar Time is OFF. Values can range from
Air Cleaner - Cumulative Run Time default is 0 hours (OFF) and Calendar Time is OFF. Values can range from
INPUT DEALER INFO
Contractors are able to input Brand Name, Unit Model Number, Contractor Name, and Contractor Phone number into these screens. This way, the owner could give this information to the contractor so that he would know what system the owner has prior to the service visit.
INPUT DEALER INFO |
|
| DEALER INFO |
|
| BRAND NAME | |
BRAND NAME |
| ||
MODEL NUMBER |
| USE ∇∆ TO SCROLL | |
CONTRACTOR NAME |
| THRU CHARACTERS | |
|
|
| |
CONTRACTOR PHONE |
| A | |
SAVE |
| A | _____________________________ |
SELECT OPTION ∇∆ |
|
| |
| CHANGE LETTER ∇∆ | ||
⊲ PREVIOUS |
| ⊲ PREVIOUS |
1.Scroll to the info you want to enter and press the center button ■.
2.Enter the information by scroll through the characters using the up & down arrows ▲▼. Once the character you want is set, press the right arrow ► to move to the next space and begin entering another character.
3.Once you’ve completed filling out the field, press the center button ■ to save the entry and return to the INPUT DEALER INFO screen. Repeat this process for all fields you want saved.
4.Once all fields have been entered, scroll to SAVE and press the center button ■.
FAN WITH HEAT OPTION
Options are ON or OFF. This selection determines whether G (fan) output is to be ON or OFF when W (auxiliary heat) output is ON. Default is ON.
DEHUMIDIFICATION CONTROL
If your system is equipped with dehumidification circuit, this output controls that function.
OCCUPIED ONLY
FULL TIME DEHUMIDIFY
NONE
DIFFERENTIAL
To adjust the Set Point for Dehumidification, Select the RH from the Main menu. The values can be selected and adjusted from that screen. Range is
NOTE: Humidity can be displayed even if not being actively controlled.
OCCUPIED ONLY - Turns on the D output when the room humidity is above the set humidity level only during the OCCUPIED (ACTIVE) time.
4