Bard CH4S1, CH5S1, CH3S1 Table Ch Dehumidifier Performance, Water Removal lb./hr PPD, Bulb, Temp

Models: CH3S1 CH5S1 CH4S1

1 14
Download 14 pages 10.23 Kb
Page 6
Image 6
TABLE 1

TABLE 1

CH DEHUMIDIFIER PERFORMANCE

Dry

 

 

Water Removal lb./hr (PPD)

 

 

Bulb

 

 

Relative Humidity % Rh

 

 

Temp

 

 

 

 

 

 

 

50

55

60

65

70

75

80

F

 

 

 

 

 

 

 

 

65

1.0 (24.0)

1.3 (31.2)

1.5 (36.0)

1.7 (40.8)

2.0 (48.0)

2.2 (52.8)

2.4 (57.6)

 

 

 

 

 

 

 

 

70

1.2 (28.8)

1.5 (36.0)

1.8 (43.2)

2.0 (48.0)

2.3 (55.2)

2.6 (62.4)

2.8 (67.2)

 

 

 

 

 

 

 

 

75

1.4 (33.6)

1.7 (40.8)

2.0 (48.0)

2.4 (57.6)

2.7 (64.8)

3.0 (72.0)

3.3 (79.2)

 

 

 

 

 

 

 

 

80

1.7 (40.8)

2.0 (46.0)

2.4 (57.6)

2.7 (64.8)

2.8 (67.2)

3.4 (81.6)

3.7 (88.8)

 

 

 

 

 

 

 

 

85

2.0 (48.0)

2.3 (55.2)

2.8 (67.2)

3.1 (74.4)

3.5 (84.0)

3.9 (93.6)

4.3 (103.2)

 

 

 

 

 

 

 

 

90

2.2 (52.8)

2.7 (64.8)

3.1 (74.4)

3.6 (86.4)

4.0 (96.0)

44 (105.6)

4.8 (115.2)

 

 

 

 

 

 

 

 

Notes: Dry Bulb Temperature F and % RH are the return air conditions to the CH unit One pint of water = 1.04 lb.

Manual

2100-506D

Page

6 of 14

Page 6
Image 6
Bard CH4S1, CH5S1, CH3S1 installation instructions Table Ch Dehumidifier Performance, Water Removal lb./hr PPD, Bulb, Temp