Bard CH5S1, CH4S1, CH3S1 System Refrigerant Pressure Chart, Table Charging Pressure Label

Models: CH3S1 CH5S1 CH4S1

1 14
Download 14 pages 10.23 Kb
Page 7
Image 7
TABLE 2

TABLE 2

CHARGING PRESSURE LABEL

SYSTEM REFRIGERANT PRESSURE CHART

Return Air

Pressure

 

 

Relative Humidity %

 

 

Temperature

 

 

 

 

 

 

 

50% RH

55% RH

60% RH

65% RH

70% RH

75% RH

80% RH

 

70° DB

Low Side

96

97

98

100

102

104

106

High Side

248

253

258

261

265

269

273

 

75° DB

Low Side

110

112

114

116

117

118

120

High Side

270

276

282

288

294

298

303

 

80° DB

Low Side

115

119

123

127

132

136

140

High Side

297

306

315

324

333

342

351

 

85° DB

Low Side

120

127

134

141

148

153

158

High Side

342

349

356

363

370

375

380

 

Low Side pressure: ±2° High Side Pressure:±5°

Table is based upon rated CFM (airflow) across the Evaporator Coil. If there is any doubt as to the correct operating charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.

Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V

7961-679

Manual

2100-506D

Page

7 of 14

Page 7