SYMPTOM
Motor starts but runs erratically
∃Varies up and down or intermittent
∃"Hunts" or puffs" at high CRM (speed)
∃Stays at low CFM despite sysstem call for cool or heat CFM
∃Stays at high CFM
∃Blower wo'nt shut off
SYMPTON
Excessive noise
∃Air Noise
CAUSE / PROCEDURE
∃Check line voltage for variation or "sag"
∃Check low voltage connections (G, Y, W, R, C) at motor; unseated pins in motor harness connectors
∃Check "Bk" for erratic CFM command (in variable speed applications
∃Check out system controls - thermostat?
∃Perform Moisture Check
∃Does removing panel or filter reduce "puffing"?
–Reduce restriction
–Reduce maximum airflow
∃Check low voltage (thermostat) wires and connections
∃Verify fan is not in dalay mode - wait until delay is complete
∃"R" missing / not connected at motor Perform motor / control replacement check
∃"R" missing / not connected at motor
∃Is fan in dalay mode? - wait until delay time complete
∃Current leakage from controls into G, Y or W?
–Check for Triac switched thermostat or solid state relay
CAUSE / PROCEDURE
∃Determine if it is air noise, cabinet, duct or motor noise . Interview customer if necessry.
∃High static creating high blower speed?
–Is airflow set properly?
–Does removing filter cause blower to slow down? Check / replace filter
–Use low pressure drop filter
–Check / correct duct restirctions
DO
∃Size the equpment wisely
∃Check orientation before inserting motor connectors
DON'T
∃Oversize system then compensate with low airflow
∃Plug in power connector backwards
∃Force plugs
MOISTURE CHECK PROCEDURE | COMFORT CHECK PROCEDURE | |||
∃ | Connectors are oriented "down" | ∃ | Check proper airflow settings | |
∃ | Arrange harnesses with "drip loop" under motor | ∃ | Low static pressure for lowest noise | |
∃ | Condenste drain plugged? | ∃ | Set low continuous fan CFM | |
∃ Check for low airflow (too much latent capacity) | ∃ | Use humidistat and | ||
∃ | Check for undercharged condition | ∃ | Use zoning controls designed for ICM that regulate CFM | |
∃ Check and plug leaks in reutrn ducts and cabinet | ∃ | Thermostat in bad location? | ||
|
|
|
| |
Manual |
|
| ||
Page | 24 |
|
|