Bard P1148A2, P1248A2, P1230A1 Service and Troubleshooting, Service Hints, Pressure Service Ports

Models: P1230A1 P1124A2 P1148A2 P1236A1 P1248A2 P1224A1 P1130A2 P1242A1 P1136A2

1 26
Download 26 pages 19.67 Kb
Page 21
Image 21

SERVICE AND TROUBLESHOOTING

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.

2.Check all power fuses or circuit breakers to be sure that they are the correct rating.

3.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in this manual covering all models on cooling cycle. It is imperative to match the correct pressure table to the unit by model number.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 11.

TABLE 11

SUCTION LINE TEMPERATURES

 

Rated

95° OD

82° OD

Model

Airflow

Temperature

Temperature

 

 

 

 

P1124A2

800

56 - 58

63 - 65

 

 

 

 

P1224A1

800

56 - 58

63 - 65

P1130A2

1125

56 - 58

63 - 65

 

 

 

 

P1230A1

1000

56 - 58

63 - 65

P1136A2

1250

57 - 59

58 - 60

 

 

 

 

P1236A1

1100

57 - 59

58 - 60

P1142A3

1400

57 - 59

58 - 60

 

 

 

 

P1242A1

1400

57 - 59

58 - 60

P1148A2

1550

54 - 57

58 - 60

 

 

 

 

P1248A2

1550

53 - 55

56 - 58

P1060A1

1700

47 - 49

54 - 56

 

 

 

 

The above suction line temperatures are based upon 80°F dry bulb/67°F wet bulb (50% RH) temperature and rated airflow across the evaporator during cooling cycle.

FAN BLADE SETTINGS

Shown in Figure 10 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 10

FAN BLADE SETTING

TABLE 12

FAN BLADE SETTING DIMENSIONS

Model

Dimension "A"

 

 

P1124A2

1.00"

 

 

P1224A1

1.00"

P1130A2

.75"

 

 

P1230A1

1.00"

P1136A2

1.00"

 

 

P1236A1

1.00"

P1142A3

1.75"

 

 

P1242A1

1.75"

P1148A2

1.75"

 

 

P1248A2

1.75"

 

 

P1060A1

1.75"

 

 

Manual 2100-353 Page 19

Page 21
Image 21
Bard P1148A2 Service and Troubleshooting, Service Hints, Pressure Service Ports, Refrigerant Charge, FAN Blade Settings