2100-444-003A
Page 72
allows the Shelter Alarm indicator to be reset to capture and indicate any new incoming Alarms.
The Zone Temperature and Humidity have four possible states. The first of which is OK and
indicates that the values are with in the set ranges. The second state would be a High Alarm condition,
stating that the value is above the High Alarm setpoint for that value. The third possible state would be
the Low Alarm condition, stating that the value is below the Low Alarm setpoint. The last alarm state is
fault alarm indicating that the sensor is reading an out of bounds condition.
6.4.4.5 Zone Humidity Alarm
If the Zone Humidity exceeds the High or Low Alarm Humidity setpoints, then the Shelter
Alarm indicator on the Main Screen will flash. A High or Low Alarm will be shown in the Alarm status
textbox on the Alarm Screen. The Shelter Alarm indicator on the Main Screen will flash until the Alarm
has been acknowledged or the Zone Humidity is no longer in Alarm. Once the alarm has been
acknowledged, the Shelter Alarm will no longer flash for the Zone Humidity Alarm. This allows the
Shelter Alarm indicator to be reset to capture and indicate any new incoming Alarms.
The Zone Temperature and Humidity have four possible states. The first of which is OK and
indicates that the values are with in the set ranges. The second state would be a High Alarm condition,
stating that the value is above the High Alarm setpoint for that value. The third possible state would be
the Low Alarm condition, stating that the value is below the Low Alarm setpoint. The last alarm state is
fault alarm indicating that the sensor is reading an out of bounds condition.
6.4.4.6 Outdoor Temperature Alarm
If the Outdoor Temperature sensor exceeds the High or Low Fault setpoints, then the Shelter
Alarm indicator on the Main Screen will flash. A Fault Alarm will be shown in the Alarm status textbox
on the Alarm Screen. The Shelter Alarm indicator on the Main Screen will flash until the Alarm has
been acknowledged or the Outdoor Temperature Sensor is no longer in a fault conditions. Once the
alarm has been acknowledged, the Shelter Alarm will no longer flash for the Outdoor Temperature
Alarm. This allows the Shelter Alarm indicator to be reset to capture and indicate any new incoming
Alarms.
6.4.4.7 Outdoor Humidity Alarm
If the Outdoor Humidity exceeds the High or Low Fault setpoints, then the Shelter Alarm
indicator on the Main Screen will flash. A High or Low Alarm will be shown in the Alarm status
textbox on the Alarm Screen. The Shelter Alarm indicator on the Main Screen will flash until the Alarm
has been acknowledged or the Outdoor Humidity Sensor is no longer in a fault condition. Once the alarm
has been acknowledged, the Shelter Alarm will no longer flash for the Outdoor Humidity Alarm. This
allows the Shelter Alarm indicator to be reset to capture and indicate any new incoming Alarms.
6.4.4.8 Main Power Alarm
If Main Power fails, the Shelter Alarm indicator on the Main Screen will flash. The Shelter