Bard W60A, W17A Indoor Blower Performance CFM at Rated Volts, Heater Packages Field Installed

Models: W17A W60A

1 12
Download 12 pages 63.13 Kb
Page 9
Image 9

Indoor Blower Performance - CFM at Rated Volts

ESP

W17A1

W24A1

W30A1

W42A1

W60A1

W18A1

W36A1

W48A1

 

 

 

in

 

 

 

 

 

 

 

 

 

H2O

High Speed

Low Speed

Single Speed

High Speed

Low Speed

High Speed

Low Speed

High Speed

Low Speed

 

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

Dry/Wet Coil

 

 

 

 

 

 

 

 

 

 

0

925/885

670/655

1020/975

1395/1315

950/935

1885/1800

1650/1600

2200/2000

1600/1450

 

 

 

 

 

 

 

 

 

 

.1

875/845

650/630

960/905

1340/1270

930/915

1770/1665

1550/1500

2100/1900

1525/1375

 

 

 

 

 

 

 

 

 

 

.2

825/795

625/600

865/800

1285/1190

910/885

1635/1550

1450/1400

2000/1800

1465/1200

 

 

 

 

 

 

 

 

 

 

.3

775/740

575/555

820/735

1205/1100

855/830

1500/1400

1350/1300

1875/1700

-/-

 

 

 

 

 

 

 

 

 

 

.4

710/670

525/500

735/650

1110/1000

800/755

1370/1285

1300/1175

1775/1600

-/-

 

 

 

 

 

 

 

 

 

 

.5

635/600

465/440

615/535

1005/870

-/-

1250/1150

-/-

1650/1475

-/-

 

 

 

 

 

 

 

 

 

 

Above data is with 1" standard throwaway filter and 1" washable filter.

Speeds marked “bold” above

For optional 2" pleated filter - reduce ESP by .15 in.

are Factory Connected.

See installation instructions for maximum ESP information on various KW application.

 

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model

Nominal

 

At 240V (1)

 

 

At 208V (1)

 

 

At 480V (2)

 

 

At 460V (2)

 

KW

Kw

1-Ph Amps

3-Ph Amps

Btuh

Kw

1-Ph Amps

3-Ph Amps

Btuh

Kw

3-Ph Amps

Btuh

Kw

3-Ph Amps

Btuh

 

5.0

5.0

20.8

 

17,065

3.75

18.0

 

12,799

 

 

 

 

 

 

6.0

6.0

 

14.4

20,478

4.50

 

12.5

15,359

6.0

7.2

20,478

5.52

6.9

18,840

8.0

8.0

33.3

 

27,304

6.00

28.8

 

20,478

 

 

 

 

 

 

9.0

9.0

 

21.7

30,717

6.75

 

18.7

23,038

9.0

10.8

30,717

8.28

10.4

28,260

10.0

10.0

41.7

 

34,130

7.50

36.1

 

25,598

 

 

 

 

 

 

15.0

15.0

62.5

36.1

51,195

11.25

54.1

31.2

38,396

15.0

18.0

51,195

13.80

17.3

47,099

18.0

18.0

 

43.3

61,434

13.50

 

37.5

46,076

18.0

21.7

61,434

16.56

20.8

56,519

20.0

20.0

83.3

 

68,260

15.00

72.1

 

51,195

 

 

 

 

 

 

(1)These electric heaters are available in 230/208V units only.

(2)These electric heaters are available in 480V units only.

Heater Packages - Field Installed

• Designed for adding Electric Heat to 0 KW Units

 

• ETL US & Canada Listed

 

 

 

• Circuit Breaker Standard on 230/208V Models

 

• Toggle Disconnect Standard on 460V Models

 

Air Conditioner

-A00 Models

 

-B00 Models

 

 

-C00 Models

 

230/208-1

 

230/208-3

 

 

460-3

 

Models

 

 

 

 

Heater Model #

KW

Heater Model #

 

KW

Heater Model #

KW

 

 

W17A1

EHWA02-A05

5

 

 

 

 

 

EHW02A-A08

8

N/A

 

N/A

 

W18A1

 

 

EHWA02A-A10

10

 

 

 

 

 

 

 

 

 

 

 

 

EHWA02-A05

5

 

 

 

 

 

W24A1

EHW02A-A08

8

EHWA24-B06

 

6

EHWH24B-C06

6

 

EHWA02A-A10

10

 

 

 

 

 

 

EHWA03-A05

5

EHWA03-B06

 

6

EHWC03A-C06

6

 

EHWA03-A08

8

 

W30A1

EHWA03-B09

 

9

EHWC03A-C09

9

EHWA03-A10

10

 

 

EHWA37-B15

 

15

EHWA03A-C15

15

 

EHWA03-A15

15

 

 

 

 

 

 

 

 

EHWA03-A05

5

EHW36A-B06

 

6

EHWC03A-C06

6

 

EHWA03-A08

8

 

W36A1

EHWA03-B09

 

9

EHWC03A-C09

9

EHWA03-A10

10

 

 

EHWA37-B15

 

15

EHWA03A-C15

15

 

EHWA03-A15

15

 

 

 

 

 

 

 

 

EHWA05-A05 1

5

EHWA05-B09 1

 

9

EHWA05A-C09 1

9

W42A1

EHWA05-A10 1

10

 

EHWA05-B15

 

15

EHWA05A-C15

15

W48A1

EHWA05-A15

15

 

EHW05A-B18 1

 

18

 

 

 

EHWA05-A20

20

 

 

 

 

 

 

 

 

 

 

EHWA60-A05 1

5

EHW60A-B09 1

 

9

EHWA05A-C09 1

9

 

EHWA05-A10 1

10

 

W60A1

EHWA05-B15 1

 

15

EHWA05A-C15

15

EHWA05-A15

15

 

 

EHW05A-B18 1

 

18

 

 

 

EHWA05-A20

20

 

 

 

 

 

 

 

 

 

NOTE: Field installed Heater Packages are not approved for use with top supply opening models.

1These heater packages approved for use in dehumidification versions with hot gas reheat.

Form No.

S3397-1112

Supersedes

S3397-712

Page

9 of 12

Page 9
Image 9
Bard W60A Indoor Blower Performance CFM at Rated Volts, Heater Packages Field Installed, High Speed, Are Factory Connected