Cooling Application Data - Outdoor Temperature 1
Model | D.B./W.B. | Cooling | 75oF | 80oF | 85oF | 90oF | 95oF | 100oF |
| 105oF | 110oF | 115oF |
| 120oF |
| 2 | Capacity |
|
|
|
|
|
|
|
|
|
|
|
|
| 75/ | Total Cooling | 17,500 | 16,700 | 15,900 | 15,100 | 14,300 | 13,600 |
| 12,900 | 12,200 | 11,600 |
| 10,800 |
| 62 | Sensible Cooling | 13,900 | 13,500 | 13,200 | 12,800 | 12,500 | 12,200 |
| 11,800 | 11,500 | 11,100 |
| 10,700 |
W17A1 | 80/ | Total Cooling | 18,600 | 18,100 | 17,600 | 17,000 | 16,400 | 15,800 |
| 15,200 | 14,500 | 13,900 |
| 13,100 |
W18A1 | 67 | Sensible Cooling | 13,400 | 13,200 | 13,000 | 12,800 | 12,600 | 12,400 |
| 12,100 | 11,800 | 11,500 |
| 11,200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 85/ | Total Cooling | 22,200 | 21,200 | 20,200 | 19,200 | 18,300 | 17,300 |
| 16,400 | 15,500 | 14,600 |
| 13,700 |
| 72 | Sensible Cooling | 13,800 | 13,400 | 13,100 | 12,800 | 12,400 | 12,000 |
| 11,600 | 11,100 | 10,600 |
| 10,200 |
| 75/ | Total Cooling | 26,000 | 24,500 | 23,300 | 22,100 | 20,900 | 20,000 |
| 19,100 | 18,400 | 17,600 |
| 17,100 |
| 62 | Sensible Cooling | 20,100 | 19,700 | 19,200 | 18,800 | 18,400 | 17,900 |
| 17,400 | 16,900 | 16,400 |
| 15,900 |
W24A1 | 80/ | Total Cooling | 27,700 | 26,700 | 25,800 | 24,900 | 24,000 | 23,300 |
| 22,500 | 21,900 | 21,200 |
| 20,700 |
67 | Sensible Cooling | 19,500 | 19,300 | 19,000 | 18,800 | 18,500 | 18,200 |
| 17,800 | 17,400 | 17,000 |
| 16,600 | |
|
|
| ||||||||||||
| 85/ | Total Cooling | 33,000 | 31,200 | 29,700 | 28,100 | 26,700 | 25,500 |
| 24,300 | 23,300 | 22,300 |
| 21,500 |
| 72 | Sensible Cooling | 20,000 | 19,600 | 19,100 | 18,700 | 18,200 | 17,600 |
| 17,000 | 16,300 | 15,700 |
| 15,000 |
| 75/ | Total Cooling | 31,100 | 29,700 | 28,300 | 27,000 | 25,800 | 24,700 |
| 23,700 | 22,700 | 21,700 |
| 20,900 |
| 62 | Sensible Cooling | 24,500 | 24,000 | 23,500 | 22,900 | 22,400 | 21,800 |
| 21,300 | 20,700 | 20,100 |
| 19,500 |
W30A1 | 80/ | Total Cooling | 33,200 | 32,300 | 31,400 | 30,400 | 29,600 | 28,600 |
| 27,800 | 27,000 | 26,100 |
| 25,300 |
67 | Sensible Cooling | 23,700 | 23,500 | 23,200 | 22,900 | 22,600 | 22,200 |
| 21,800 | 21,400 | 20,900 |
| 20,400 | |
|
|
| ||||||||||||
| 85/ | Total Cooling | 39,600 | 37,800 | 36,100 | 34,500 | 32,900 | 31,500 |
| 30,100 | 28,800 | 27,500 |
| 26,300 |
| 72 | Sensible Cooling | 24,300 | 23,900 | 23,300 | 22,800 | 22,200 | 21,500 |
| 20,800 | 20,100 | 19,300 |
| 18,500 |
| 75/ | Total Cooling | 38,100 | 35,900 | 34,100 | 32,300 | 30,800 | 29,600 |
| 28,600 | 27,700 | 26,900 |
| 26,400 |
| 62 | Sensible Cooling | 28,500 | 27,800 | 27,100 | 26,400 | 25,800 | 25,200 |
| 24,700 | 24,200 | 23,700 |
| 23,200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
W36A1 | 80/ | Total Cooling | 40,600 | 39,100 | 37,800 | 36,500 | 35,400 | 34,500 |
| 33,700 | 33,000 | 32,400 |
| 32,000 |
67 | Sensible Cooling | 27,600 | 27,200 | 26,800 | 26,400 | 26,000 | 25,600 |
| 25,300 | 25,000 | 24,600 |
| 24,300 | |
|
|
| ||||||||||||
| 85/ | Total Cooling | 48,400 | 45,700 | 43,400 | 41,200 | 39,300 | 37,800 |
| 36,400 | 35,100 | 34,100 |
| 33,300 |
| 72 | Sensible Cooling | 28,300 | 27,600 | 26,900 | 26,200 | 25,500 | 24,800 |
| 24,100 | 23,500 | 22,700 |
| 22,000 |
| 75/ | Total Cooling | 43,600 | 41,500 | 39,600 | 37,600 | 35,700 | 33,900 |
| 32,100 | 30,400 | 28,700 |
| 27,000 |
| 62 | Sensible Cooling | 35,500 | 34,500 | 33,600 | 32,700 | 31,800 | 31,000 |
| 30,100 | 29,200 | 28,400 |
| 27,000 |
W42A1 | 80/ | Total Cooling | 46,500 | 45,200 | 43,900 | 42,500 | 41,000 | 39,500 |
| 37,900 | 36,200 | 34,500 |
| 32,700 |
67 | Sensible Cooling | 34,400 | 33,800 | 33,300 | 32,700 | 32,100 | 31,500 |
| 30,900 | 30,200 | 29,500 |
| 28,800 | |
|
|
| ||||||||||||
| 85/ | Total Cooling | 55,400 | 52,900 | 50,400 | 48,000 | 45,600 | 43,200 |
| 40,900 | 38,500 | 36,300 |
| 34,000 |
| 72 | Sensible Cooling | 35,200 | 34,300 | 33,500 | 32,500 | 31,500 | 30,500 |
| 29,500 | 28,300 | 27,200 |
| 26,000 |
| 75/ | Total Cooling | 49,600 | 47,300 | 45,100 | 43,000 | 40,900 | 39,000 |
| 37,100 | 35,100 | 33,300 |
| 31,400 |
| 62 | Sensible Cooling | 39,900 | 39,100 | 38,200 | 37,300 | 36,400 | 35,500 |
| 34,500 | 33,600 | 32,700 |
| 31,400 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
W48A1 | 80/ | Total Cooling | 52,900 | 51,500 | 50,100 | 48,600 | 47,000 | 45,400 |
| 43,700 | 41,900 | 40,000 |
| 38,100 |
67 | Sensible Cooling | 38,700 | 38,300 | 37,800 | 37,300 | 36,700 | 36,100 |
| 35,400 | 34,700 | 34,000 |
| 33,100 | |
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 85/ | Total Cooling | 63,000 | 60,200 | 57,500 | 54,900 | 52,200 | 49,700 |
| 47,100 | 44,600 | 42,000 |
| 39,600 |
| 72 | Sensible Cooling | 39,600 | 38,900 | 38,000 | 37,100 | 36,000 | 34,900 |
| 33,800 | 32,500 | 31,300 |
| 29,900 |
| 75/ | Total Cooling | 59,200 | 56,200 | 53,300 | 50,500 | 47,900 | 45,400 |
| 43,100 | 40,800 | 38,600 |
| 36,600 |
| 62 | Sensible Cooling | 45,200 | 43,800 | 42,300 | 41,000 | 39,700 | 38,500 |
| 37,300 | 36,100 | 35,000 |
| 33,900 |
W60A1 | 80/ | Total Cooling | 63,200 | 61,200 | 59,200 | 57,100 | 55,000 | 52,900 |
| 50,800 | 48,700 | 46,500 |
| 44,300 |
67 | Sensible Cooling | 43,800 | 42,900 | 41,900 | 41,000 | 40,100 | 39,200 |
| 38,300 | 37,300 | 36,400 |
| 35,500 | |
|
|
| ||||||||||||
| 85/ | Total Cooling | 75,300 | 71,600 | 68,000 | 64,500 | 61,100 | 57,900 |
| 54,800 | 51,800 | 48,900 |
| 46,000 |
| 72 | Sensible Cooling | 44,900 | 43,600 | 42,100 | 40,700 | 39,300 | 37,900 |
| 36,500 | 35,000 | 33,500 |
| 32,100 |
|
|
|
|
|
|
|
|
| Capacity Multiplier Factors |
| ||||
|
|
|
|
|
|
|
| % of Rated Airflow | Rated |
| +10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Total BTUH | 0.975 | 1.0 |
| 1.02 | |
|
|
|
|
|
|
|
| Sensible BTUH | 0.950 | 1.0 |
| 1.05 |
1Below 65°F (18.3C), unit requires a factory or field installed low ambient control.
2 Return air temperature.
Form No. | |
Supersedes | |
Page | 10 of 12 |