TABLE 5

RECOMMENDED AIRFLOW

 

Nominal

Nominal

Recommended

Factory Speed

Model

Rated

Rated

Airflow Range

Connection

 

CFM *

ESP *

 

 

 

 

W17A, W17L

600

.40

550

- 725

Low

 

 

 

 

 

 

W18A, W18L

550

.45

550

- 725

Low

W24A, W24L

800

.30

700

- 950

Single

W30A, W30L

1000

.30

850 - 1300

High

 

 

 

 

 

W36A, W36L

1100

.20

930 - 1350

High

W42A, W42L

1400

.45

1600 - 1150

High

 

 

 

 

 

 

W48A, W48L

1550

.30

1750

- 1285

High

W60A, W60L

1700

.40

1950

- 1375

High

 

 

 

 

 

 

W70A, W70L

1700

.20

1950

- 1375

High

* Rated CFM and ESP on factory speed connection.

TABLE 6

INDOOR BLOWER PERFORMANCE

Speed

 

W17/18

 

W24

 

W30

 

 

W36

 

 

W42/48

 

 

W60

 

 

W70

 

High

Low

Single

High

Low

High

Low

High

Low

High

Low

High

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

(Inch

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

H20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

1045

1025

760

745

990

970

1370

1285

910

885

1415

1275

955

925

1850

1800

1605

1555

2080

2015

1505

1460

2050

1845

1490

1400

0.1

1010

970

730

715

945

925

1305

1225

885

860

1350

1215

945

915

1775

1725

1545

1500

2020

1960

1450

1405

1970

1770

1425

1340

0.2

940

905

700

685

890

870

1225

1135

850

815

1265

1125

925

900

1685

1640

1460

1415

1925

1865

1395

1355

1905

1700

1375

1295

0.3

860

830

670

655

820

800

1115

1020

790

755

1190

1060

875

850

1590

1550

1390

1345

1870

1815

1340

1300

1830

1645

1225

1150

0.4

780

750

610

595

735

720

1005

910

695

660

1085

975

780

755

1495

1460

1310

1270

1755

1705

1225

1185

1725

1550

1140

1070

0.5

665

640

485

455

605

590

865

775

590

560

970

865

640

615

1400

1365

1225

1185

1660

1610

1125

1085

1500

1350

1050

985

TABLE 7

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

 

W17A/L,

 

 

 

 

 

 

 

 

 

Model

W18A/L,

 

W30A/L, W36A/L

 

W42A/L, W48A/L

W60A/L, W70A/L

 

W24A/L

 

 

 

 

 

 

 

 

 

Outlet

FRONT

FRONT

TOP

 

FRONT

FRONT

Speed

Single

High

Low

High

 

Low

High

Low

High

Low

-A0Z

.50

.50

.50

.50

 

.50

.50

.50

.50

.50

-A04

 

 

 

.50

 

.45

 

 

 

 

-A05

.50

.50

.50

 

 

 

.50

.50

.50

.50

-A08

.50

.50

.50

 

 

 

 

 

 

 

-A10

 

.50

.45

.50

 

.35

.50

.50

.50

.50

-A15

 

.40

.35

 

 

 

.50

.50

.50

.50

-A20

 

 

 

 

 

 

.50

.45

.50

.40

-B0Z

.50

.50

.50

.50

 

.50

.50

.50

.50

.50

-B06

.50

.50

.40

 

 

 

 

 

 

 

-B09

 

.50

.50

.45

 

.40

.50

.50

.50

.50

-B15

 

.45

.30

 

 

 

.50

.50

.50

.50

-B18

 

 

 

 

 

 

.50

.50

.50

.50

-C0Z

 

.50

.50

.50

 

.50

.50

.50

.50

.50

-C06

 

.50

.50

 

 

 

 

 

 

 

-C09

 

.50

.40

.45

 

.40

.50

.50

.50

.50

-C15

 

.45

.35

 

 

 

.50

.50

.50

.50

Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter.

Derate ESP by .15 for 2-inch pleated filters.

Manual

2100-581B

Page

22 of 26

Page 22
Image 22