Bard W61A1, W49A1, W38A1 manual Electrical Specifications, Single Circuit, Dual Circuit

Models: W38A1 W61A1 W49A1

1 12
Download 12 pages 29.53 Kb
Page 4
Image 4
Electrical Specifications

Electrical Specifications

 

 

 

 

Single Circuit

 

 

 

 

Dual Circuit

 

 

 

 

Rated

No. Field

3 Minimum

1 Maximum

2 Field

 

3 Minimum

1 Maximum

2 Field

2 Ground

 

2 Ground

Circuit

External Fuse

Power

Model

Volts

Power

Circuit

External Fuse

Power

Wire Size

Wire

Ampacity

or Ckt. Brkr.

Wire Size

 

and Phase

Circuits

Ampacity

or Ckt. Brkr.

Wire Size

 

 

 

 

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

Ckt. B

 

 

 

 

 

 

 

W38A1 - A0Z

 

1

32

45

8

10

 

 

 

 

 

 

 

 

A05

 

1

35

45

8

10

 

 

 

 

 

 

 

 

A08

230/208-1

1

50

50

8

10

 

 

 

 

 

 

 

 

A10

 

1 or 2

61

70

6

8

35

26

45

30

8

10

10

10

A15

 

1 or 2

87

90

3

8

35

52

45

60

8

6

10

10

W38A1 - B0Z

 

1

26

35

8

10

 

 

 

 

 

 

 

 

B06

230/208-3

1

27

35

8

10

 

 

 

 

 

 

 

 

B09

1

36

40

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B15

 

1

54

60

6

10

 

 

 

 

 

 

 

 

W38A1 - C0Z

 

1

14

15

14

14

 

 

 

 

 

 

 

 

C06

460-3

1

15

15

14

14

 

 

 

 

 

 

 

 

C09

1

19

20

12

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C15

 

1

28

30

10

10

 

 

 

 

 

 

 

 

W49A1 - A0Z

 

1

39

50

8

10

 

 

 

 

 

 

 

 

A05

 

1

39

50

8

10

 

 

 

 

 

 

 

 

A08

230/208-1

1

51

60

6

10

 

 

 

 

 

 

 

 

A10

 

1 or 2

61

70

6

8

39

26

50

30

8

10

10

10

A15

 

1 or 2

87

90

3

8

39

52

50

60

8

6

10

10

W49A1 - B0Z

 

1

30

45

8

10

 

 

 

 

 

 

 

 

B06

230/208-3

1

30

45

8

10

 

 

 

 

 

 

 

 

B09

1

37

45

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B15

 

1

55

60

6

10

 

 

 

 

 

 

 

 

W49A1 - C0Z

 

1

15

20

12

12

 

 

 

 

 

 

 

 

C06

460-3

1

15

20

12

12

 

 

 

 

 

 

 

 

C09

1

19

20

12

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C15

 

1

28

30

10

10

 

 

 

 

 

 

 

 

W61A1 - A0Z

 

1

48

60

8

10

 

 

 

 

 

 

 

 

A05

 

1

48

60

8

10

 

 

 

 

 

 

 

 

A08

230/208-1

1

51

60

6

8

 

 

 

 

 

 

 

 

A10

 

1 or 2

61

70

6

8

48

26

60

30

6

10

10

10

A15

 

1 or 2

87

90

3

8

48

52

60

60

6

6

10

10

W61A1- B0Z

 

1

36

50

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

37

50

8

10

 

 

 

 

 

 

 

 

B15

 

1

55

60

6

10

 

 

 

 

 

 

 

 

W61A1 - C0Z

 

1

18

25

10

10

 

 

 

 

 

 

 

 

C09

460-3

1

19

25

10

10

 

 

 

 

 

 

 

 

C15

 

1

28

30

10

10

 

 

 

 

 

 

 

 

1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.

3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.

Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.