Bard W38A1 Cooling Application Data - Outdoor Temperature, Capacity Multiplier Factors, Model

Models: W38A1 W61A1 W49A1

1 12
Download 12 pages 29.53 Kb
Page 8
Image 8
Cooling Application Data - Outdoor Temperature 1

Cooling Application Data - Outdoor Temperature 1

Model

D.B./W.B.

Cooling

75oF

80oF

85oF

90oF

95oF

100oF

105oF

110oF

115oF

120oF

 

2

Capacity

 

 

 

 

 

 

 

 

 

 

 

75/

Total Cooling

37,700

35,900

34,200

32,600

31,000

29,600

28,200

26,900

25,700

24,400

 

62

Sensible Cooling

28,600

27,800

27,100

26,300

25,600

24,900

24,100

23,400

22,700

22,000

W38A1

80/

Total Cooling

40,200

39,100

38,000

36,800

35,600

34,500

33,300

32,100

30,900

29,600

67

Sensible Cooling

27,700

27,200

26,800

26,300

25,800

25,300

24,700

24,200

23,600

23,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

47,900

45,700

43,700

41,600

39,600

37,800

35,900

34,200

32,500

30,800

 

72

Sensible Cooling

28,400

27,600

26,900

26,100

25,300

24,500

23,600

22,700

21,800

20,800

 

75/

Total Cooling

48,900

46,500

44,400

42,400

40,500

38,800

37,200

35,600

34,200

33,000

 

62

Sensible Cooling

36,700

35,200

33,800

32,700

31,700

31,000

30,300

29,800

29,600

29,400

W49A1

80/

Total Cooling

52,200

50,700

49,300

47,900

46,500

45,200

43,900

42,500

41,200

40,000

67

Sensible Cooling

35,600

34,500

33,500

32,700

32,000

31,500

31,100

30,800

30,800

30,800

 

 

85/

Total Cooling

62,200

59,300

56,600

54,100

51,700

49,500

47,300

45,200

43,300

41,600

 

72

Sensible Cooling

36,500

35,000

33,700

32,500

31,400

30,500

29,700

28,900

28,400

27,800

 

75/

Total Cooling

58,900

56,900

54,900

53,000

50,900

49,000

47,000

45,000

43,000

41,100

 

62

Sensible Cooling

41,400

40,600

39,800

39,000

38,100

37,200

36,100

35,000

33,800

32,700

 

 

 

 

 

 

 

 

 

 

 

 

 

W61A1

80/

Total Cooling

62,900

62,000

61,000

59,000

57,500

56,500

55,500

53,700

51,800

49,800

67

Sensible Cooling

40,100

39,800

39,400

39,000

38,400

37,800

37,000

36,200

35,200

34,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85/

Total Cooling

74,900

72,500

70,100

67,600

65,000

62,500

59,800

57,100

54,400

51,800

 

72

Sensible Cooling

41,100

40,400

39,600

38,800

37,700

36,600

35,300

34,000

32,400

30,900

1 Below 65°F (18.3C), unit requires a factory or field installed low ambient control. 2 Return air temperature.

Capacity Multiplier Factors

% of Rated Airflow

-10

Rated

+10

 

 

 

 

Total BTUH

0.975

1.0

1.02

Sensible BTUH

0.950

1.0

1.05

Form No.

S3412-1112

Supersedes

S3412-712

Page

8 of 12

Page 8
Image 8
Bard W38A1 Cooling Application Data - Outdoor Temperature, Capacity Multiplier Factors, Model, D.B./W.B, 75oF, 80oF, 85oF