Bard W49A1, W61A1, W38A1 manual Ventilation System Packages

Models: W38A1 W61A1 W49A1

1 12
Download 12 pages 29.53 Kb
Page 3
Image 3
Ventilation System Packages

Ventilation System Packages

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory or field-installed at a later date.

BAROMETRIC FRESH AIR DAMPER - BFAD

STANDARD

The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service

door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the

air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and

closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into

the building and can be easily locked closed if required.

 

BLANK OFF PLATE - BOP

OPTIONAL

Barometric Fresh Air Damper

A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any

 

 

outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not

 

required to be mixed with the conditioned air.

Motorized Fresh Air Damper

Commercial Room Ventilator

Economizer

Energy Recovery Ventilator

MOTORIZED FRESH AIR DAMPER - MFAD

OPTIONAL

The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.

COMMERCIAL ROOM VENTILATOR - CRV

OPTIONAL

The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.

The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.

ECONOMIZER - ECONWM-Series

OPTIONAL

The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

ECONWMT Equipment Building versions have extended air intake hood to deliver up to 100% of cooling rated airflow.

￿16" for ECONWMT-E2 or T2, and E3 or T3

￿18" for ECONWMT-E5 or T5

ECONWMS Classroom versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.

Standard Features:

Fully modulating

Honeywell Direct Drive Hi-Torque Actuator

No linkage required

Simple single blade design

Positive shut-off with non-stick gaskets

Electronic DB and/or Enthalpy sensors depending upon version

Honeywell JADE electronic economizer module with precision settings and diagnostics

DB or Enthalpy economizer versions available

WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF

OPTIONAL

The wall-mount energy recovery ventilator (ERVF) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERVF allows from 300 to 450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.

The ERVF consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.

The ERVF is designed to be internally mounted behind the service door in the W**A, W**H or W**L model wall- mount units. It can be built-in at the factory or field installed as an option. ERVF-*3 and ERVF-*5 can be independently adjusted for intake and exhaust rates.

Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744

Form No.

S3412-1112

Supersedes

S3412-712

Page

3 of 12

Page 3
Image 3
Bard W49A1, W61A1, W38A1 manual Ventilation System Packages