START UP
IMPORTANT INSTALLER NOTE
For improved
CRANKCASE HEATERS
All units are provided with some form of compressor crankcase heat.
All single and three phase models have an insertion
Some form of crankcase heat is essential to prevent liquid refrigerant from migrating to the compressor, causing oil pump out on compressor start up and possible valve failure due to compressing a liquid.
The decal in Figure 9 is affixed to all outdoor units detailing start up procedure. This is very important. Please read carefully.
SERVICE HINTS
1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs.
2.Check all power fuses or circuit breakers to be sure they are the correct rating.
3.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COMPRESSOR CONTROL MODULE
The compressor control module is optional on the models covered by this manual. The compressor control is an
Adjustable Delay On Make And Break Timer
On initial power up or any time power is interrupted to the unit the delay on make period begins which will be
2 minutes plus 10% of the delay on break setting. When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.
During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.
FIGURE 9
START UP LABEL
IMPORTANT
These procedures must be followed at initial start up and at any time power has been removed for 12 hours or longer.
To prevent compressor damage which may result from the presence of liquid refrigerant in the compressor crankcase:
1.Make certain the room thermostat is in the "off" position (the compressor is not to operate).
2.Apply power by closing the system disconnect switch. This energizes the compressor heater which evaporates the liquid refrigerant in the crankcase.
3.Allow 4 hours or 60 minutes per poind of refrigerant in the system as noted on the unit rating plate, whichever is greater.
4.After properly elapsed time, the thermostat may be set to operate the compressor.
5.Except as required for safety while servicing, do not open system disconnect switch.
Manual