WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
MODEL NUMBER
WA 36 1 – A 10 X X X X X A
CONTROL MODULES
CAPACITY |
| ||
30 | - | 2 1/2 Ton |
|
36 | - | 3 Ton | REVISIONS |
KW
COLOR OPTIONS
X - Beige (Standard)
1 - White
COIL OPTIONS
X - Standard
1 - Phenolic Coated Evapora- tor
2 - Phenolic Coated Con- denser
VOLTS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
VENTILATION OPTIONS
X - Barometric Fresh Air Damper
(Standard)
B -
M - Motorized Fresh Air Damper V - Commercial Room Ventilator
-
2- Mesa Brown
4 - Buckeye Gray
5 - Desert Brown
6 - Dark Bronze
3 - Phenolic Coated Evapora- tor
and Condenser
OUTLET OPTIONS
X- Front (Standard)
T - Top on WA30 and WA36
Models
Motorized with Exhaust
E - Economizer (Internal - Fully
Modulating with Exhaust
R - Energy Recovery Ventilator -
NOTE: For 0KW and circuit breakers (230/208 Volt) or pull disconnects (460 Volt) applications, insert 0Z in the KW field of with Exhaust
model number.
TABLE 1
ELECTRICAL SPECIFICATIONS
|
|
| 3 | 1 | 2 | 2 | 3 |
| 1 |
| 2 |
| 2 | ||||
|
|
|
|
|
|
|
|
| Maximum |
|
|
|
|
|
| ||
|
|
|
| Maximum |
|
| Minimum | External | Field |
|
|
| |||||
|
| No. |
| Field |
| Fuse or | Ground | ||||||||||
| Rated | Minimum | External | Ground | Circuit | Circuit | Power | ||||||||||
| Field | Fuse or | Power | Ampacity | Breaker | Wire Size | Wire Size | ||||||||||
| Volts & | Power | Circuit | Circuit. | Wire | Wire |
|
|
|
|
|
|
|
|
|
|
|
Model | CKT | CKT | CKT |
| CKT | CKT |
| CKT | CKT |
| CKT | ||||||
Phase | Circuits | Ampacity | Breaker | Size | Size |
|
|
| |||||||||
|
|
|
|
|
|
| A | B | A |
| B | A |
| B | A |
| B |
| 1 | 24 | 35 | 8 | 10 |
|
|
| |||||||||
A05 | 1 | 31 | 35 | 8 | 10 |
|
|
| |||||||||
A10 | 1 | 57 | 60 | 6 | 10 |
|
|
| |||||||||
A15 |
| 1 or 2 | 83 | 90 | 4 | 8 | 55 | 26 | 60 |
| 30 | 4 |
| 10 | 8 |
| 10 |
| 1 | 17 | 20 | 12 | 12 |
|
|
| |||||||||
B09 | 1 | 32 | 35 | 8 | 10 |
|
|
| |||||||||
B15 |
| 1 | 50 | 50 | 8 | 10 |
|
|
| ||||||||
| 1 | 10 | 15 | 14 | 14 |
|
|
| |||||||||
C09 | 1 | 17 | 20 | 12 | 12 |
|
|
| |||||||||
C15 |
| 1 | 26 | 30 | 10 | 10 |
|
|
| ||||||||
| 1 | 27 | 35 | 8 | 10 |
|
|
| |||||||||
A05 | 1 | 31 | 35 | 8 | 10 |
|
|
| |||||||||
A10 | 1 | 57 | 60 | 6 | 10 |
|
|
| |||||||||
A15 |
| 1 or 2 | 83 | 90 | 4 | 8 | 55 | 26 | 60 |
| 30 | 4 |
| 10 | 8 |
| 10 |
| 1 | 20 | 25 | 10 | 10 |
|
|
| |||||||||
B09 | 1 | 32 | 35 | 8 | 10 |
|
|
| |||||||||
B15 |
| 1 | 50 | 50 | 8 | 10 |
|
|
| ||||||||
| 1 | 10 | 15 | 14 | 14 |
|
|
| |||||||||
C09 | 1 | 17 | 20 | 12 | 12 |
|
|
| |||||||||
C15 |
| 1 | 26 | 30 | 10 | 10 |
|
|
|
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75° copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual
Page 2