Bard WA361, WA301 installation instructions Table Maximum Esp Of Operation Electric Heat Only

Models: WA301 WA361

1 19
Download 19 pages 18.14 Kb
Page 18
Image 18
TABLE 11

TABLE 11

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

Front Outlet

Top Outlet

 

 

 

 

 

 

Low

High

Low

High

KW

Speed

Speed

Speed

Speed

A00

.50

.50

.50

.50

A05

.50

.50

.45

.50

A08

.50

.50

---

---

A10

.45

.50

.35

.50

A15

.35

.40

---

---

 

 

 

 

 

B00

.50

.50

.50

.50

B06

.40

.50

---

---

B09

.50

.50

.40

.45

B15

.30

.45

---

---

 

 

 

 

 

C00

.50

.50

.50

.50

C06

.50

.50

---

---

C09

.40

.50

.40

.45

C15

.35

.45

---

---

 

 

 

 

 

TABLE 12

COOLING PRESSURE – OUTDOOR TEMPERATURE °F

 

Return Air

 

 

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

110

115

120

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg DB

Low Side

74

77

79

81

82

84

85

85

86

87

88

 

62 deg WB

High Side

218

232

247

262

277

292

306

325

341

357

373

WA301

80 deg DB

Low Side

80

82

84

86

88

89

91

91

92

93

94

67 deg WB

High Side

223

238

253

268

284

300

316

333

350

366

383

 

 

85 deg DB

Low Side

85

88

91

93

95

96

97

96

99

100

101

 

72 deg WB

High Side

231

246

262

278

294

310

327

345

362

379

396

 

75 deg DB

Low Side

70

72

74

76

78

79

80

81

82

83

84

 

62 deg WB

High Side

224

242

259

275

290

304

316

328

339

351

363

WA361

80 deg DB

Low Side

75

77

79

81

83

85

86

87

88

89

90

67 deg WB

High Side

229

248

265

272

297

311

325

337

348

360

373

 

 

85 deg DB

Low Side

80

83

85

87

89

91

92

94

95

96

98

 

72 deg WB

High Side

238

257

275

292

307

322

336

349

360

373

386

Low side pressure ± 2 psig

High side pressure ± 5 psig

Tables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled "refrigerant charge" elsewhere in manual. If there is any doubt as to correct charge being in the system, the charge should be removed, system evacu- ated and recharged to serial plate instructions.

Manual 2100-192 Page 16