TABLE 11
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Model | Front Outlet | Top Outlet | ||
|
|
|
|
|
| Low | High | Low | High |
KW | Speed | Speed | Speed | Speed |
A00 | .50 | .50 | .50 | .50 |
A05 | .50 | .50 | .45 | .50 |
A08 | .50 | .50 | ||
A10 | .45 | .50 | .35 | .50 |
A15 | .35 | .40 | ||
|
|
|
|
|
B00 | .50 | .50 | .50 | .50 |
B06 | .40 | .50 | ||
B09 | .50 | .50 | .40 | .45 |
B15 | .30 | .45 | ||
|
|
|
|
|
C00 | .50 | .50 | .50 | .50 |
C06 | .50 | .50 | ||
C09 | .40 | .50 | .40 | .45 |
C15 | .35 | .45 | ||
|
|
|
|
|
TABLE 12
COOLING PRESSURE – OUTDOOR TEMPERATURE °F
| Return Air |
|
|
|
|
|
|
|
|
|
|
|
| |
Model | Temperature | Pressure | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | 120 | 125 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 75 deg DB | Low Side | 74 | 77 | 79 | 81 | 82 | 84 | 85 | 85 | 86 | 87 | 88 | |
| 62 deg WB | High Side | 218 | 232 | 247 | 262 | 277 | 292 | 306 | 325 | 341 | 357 | 373 | |
WA301 | 80 deg DB | Low Side | 80 | 82 | 84 | 86 | 88 | 89 | 91 | 91 | 92 | 93 | 94 | |
67 deg WB | High Side | 223 | 238 | 253 | 268 | 284 | 300 | 316 | 333 | 350 | 366 | 383 | ||
| ||||||||||||||
| 85 deg DB | Low Side | 85 | 88 | 91 | 93 | 95 | 96 | 97 | 96 | 99 | 100 | 101 | |
| 72 deg WB | High Side | 231 | 246 | 262 | 278 | 294 | 310 | 327 | 345 | 362 | 379 | 396 | |
| 75 deg DB | Low Side | 70 | 72 | 74 | 76 | 78 | 79 | 80 | 81 | 82 | 83 | 84 | |
| 62 deg WB | High Side | 224 | 242 | 259 | 275 | 290 | 304 | 316 | 328 | 339 | 351 | 363 | |
WA361 | 80 deg DB | Low Side | 75 | 77 | 79 | 81 | 83 | 85 | 86 | 87 | 88 | 89 | 90 | |
67 deg WB | High Side | 229 | 248 | 265 | 272 | 297 | 311 | 325 | 337 | 348 | 360 | 373 | ||
| ||||||||||||||
| 85 deg DB | Low Side | 80 | 83 | 85 | 87 | 89 | 91 | 92 | 94 | 95 | 96 | 98 | |
| 72 deg WB | High Side | 238 | 257 | 275 | 292 | 307 | 322 | 336 | 349 | 360 | 373 | 386 |
Low side pressure ± 2 psig
High side pressure ± 5 psig
Tables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled "refrigerant charge" elsewhere in manual. If there is any doubt as to correct charge being in the system, the charge should be removed, system evacu- ated and recharged to serial plate instructions.