Bard WA421 Table Recommended Airflow, Table Maximum Esp Of Operation Electric Heat Only, Cooling

Models: WA482 WA421

1 21
Download 21 pages 59.56 Kb
Page 20
Image 20
TABLE 8

TABLE 8

RECOMMENDED AIRFLOW

 

Rated

Rated

Recommended

Model

CFM *

ESP *

Airflow Range

 

 

 

 

WA421

1400

.30

1600 - 1150

 

 

 

 

WA482

1550

.20

1750 - 1285

 

 

 

 

WA602

1700

.30

1950 - 1375

 

 

 

 

* Rated CFM and ESP on high speed tap.

TABLE 9

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

WA421

WA482

WA602

 

 

 

 

 

 

 

 

High

Low

High

Low

High

Low

KW

Speed

Speed

Speed

Speed

Speed

Speed

 

 

 

 

 

 

 

-A05

.50

.50

.50

.50

.50

.50

-A10

.50

.50

.50

.50

.50

.50

-A15

.50

.50

.50

.50

.50

.50

-A20

.50

.45

.50

.45

.50

.40

 

 

 

 

 

 

 

-B00

.50

.50

.50

.50

.50

.50

-B09

.50

.50

.50

.50

.50

.50

-B15

.50

.50

.50

.50

.50

.50

-B18

.50

.50

.50

.50

.50

.50

 

 

 

 

 

 

 

-C09

.50

.50

.50

.50

.50

.50

-C15

.50

.50

.50

.50

.50

.50

 

 

 

 

 

 

 

Values shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter. Derate ESP by .15 for 2 inch pleated filters.

TABLE 10

PRESSURE TABLE

COOLING

 

 

 

Air Temperature Entering Outdoor Coil °F

 

 

 

Return Air

 

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

110

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

68

71

74

76

78

80

81

83

84

 

 

62 deg. WB

High Side

213

228

243

259

274

290

305

321

337

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA421

80 deg. DB

Low Side

72

76

79

82

84

86

88

89

90

 

67 deg. WB

High Side

218

234

249

265

281

297

313

330

346

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg. DB

Low Side

78

82

85

88

90

92

94

96

97

 

 

72 deg. WB

High Side

226

242

258

274

290

307

323

341

358

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

73

74

76

78

79

80

82

83

84

 

 

62 deg. WB

High Side

204

217

232

248

265

284

304

325

348

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA482

80 deg. DB

Low Side

78

79

81

82

84

86

87

89

90

 

67 deg. WB

High Side

210

223

238

254

272

291

312

334

357

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg. DB

Low Side

84

85

87

88

90

92

93

95

97

 

 

72 deg. WB

High Side

217

231

247

264

282

302

323

345

369

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

71

72

74

75

76

77

78

78

79

 

 

62 deg. WB

High Side

233

247

262

278

295

313

331

351

371

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA602

80 deg. DB

Low Side

76

78

79

80

81

82

83

84

85

 

67 deg. WB

High Side

237

253

269

285

303

321

340

390

381

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 deg. DB

Low Side

84

85

85

86

87

88

89

90

91

 

 

72 deg. WB

High Side

245

261

278

296

314

333

353

373

394

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG

High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.

NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See “Condenser Fan Operation” on Page 14.

Manual 2100-218