Natural Gas Orifice and Altitude Tables
|
|
| 6,001 to 8,000 Feet | 8,001 to 10,000 Feet | |
|
|
| Requires Pressure Switch | Requires Pressure Switch | |
Factory | Gas Heat* | Up to 6,000 Feet No | Change and Orifice | Change and Orifice | |
Standard | Value | Changes Except | Change | Change | |
Input | BTU/Cu. Ft. | for BTU Content | Based on BTU Content | Based on BTU Content | |
25000 BTU | 2.90 | 2.80 | 2.70 |
| |
Per Burner |
|
|
|
|
|
2.80 | 2.70 | 2.60 |
| ||
|
| ||||
|
|
|
|
|
|
| 2.70 | 2.60 | 2.50 |
| |
|
|
|
|
|
|
| 2.60 | 2.50 | 2.45 |
| |
|
|
|
|
|
|
| 2.50 | 2.45 | (2.40) |
| |
|
|
|
|
|
|
| 2.45 | (2.40) | 2.35 |
| |
|
|
|
|
|
|
| (2.40) | 2.35 | [2.30] |
| |
| [2.30] | 2.25 | 2.20 |
| |
|
|
|
|
| |
| Pressure Switch | Standard (.55) | Order |
| |
(2.40) is the standard factory installed orifice size | [2.30] orifices are shipped with the unit for field installed | ||||
|
|
| optional 10% derate |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| 6,001 to 8,000 Feet | 8,001 to 10,000 Feet | |
Optional |
|
| Requires Pressure Switch | Requires Pressure Switch | |
10% Field | Gas Heat* | Up to 6,000 Feet No | Change and Orifice | Change and Orifice | |
Converted | Value | Changes Except | Change | Change | |
Derate | BTU/Cu. Ft. | for BTU Content | Based on BTU Content | Based on BTU Content | |
22500 BTU | 2.75 | 2.70 | 2.60 |
| |
Per Burner |
|
|
|
|
|
2.70 | 2.60 | 2.50 |
| ||
|
| ||||
|
|
|
|
|
|
| 2.60 | 2.50 |
|
| |
|
|
|
|
|
|
| 2.50 | 2.45 | (2.40) |
| |
|
|
|
|
|
|
| (2.40) | 2.35 | [2.30] |
| |
|
|
|
|
|
|
| 2.35 | [2.30] | 2.25 |
| |
|
|
|
|
|
|
| [2.30] | 2.25 | 2.20 |
| |
|
|
|
|
|
|
| 2.25 | 2.25 | 2.20 |
| |
|
|
|
|
| |
| Pressure Switch | Standard (.55) | Order |
| |
[2.30] orifices are shipped with the unit for field | (2.40) is the factory installed orifice size for full rated input | ||||
installed optional 10% input rate. |
|
|
|
*At standard conditions: 30.00 inches Mercury, 60F, saturated, .60 specific gravity.
**All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU/cu ft gas and sea level conditions
All other orifice sizes shown are available as individual items. See Orifice charts below for part numbers and number required.
Bard Part No. | Orifice Size (mm) | Orifice Diameter |
|
|
|
2.10 | 0.0826 | |
|
|
|
2.15 | 0.0846 | |
|
|
|
2.20 | 0.0866 | |
|
|
|
2.25 | 0.0885 | |
|
|
|
2.30 | 0.0905 | |
|
|
|
2.35 | 0.0925 | |
|
|
|
2.40 | 0.0945 | |
|
|
|
2.45 | 0.0964 | |
2.50 | 0.0984 | |
|
|
|
2.60 | 0.1024 | |
|
|
|
2.70 | 0.1063 | |
|
|
|
2.75 | 0.1082 | |
|
|
|
2.80 | 0.1102 | |
|
|
|
2.90 | 0.1142 | |
|
|
|
No. of Orifices Required
Based on Unit Input Rating
45,000 (2)
50,000 (2)
68,000 (3)
75,000 (3)
90,000 (4)
100,000 (4)
113,000 (5)
125,000 (5)
Form No. | |
Supersedes | |
Page | 8 of 12 |