Important Information Concerning Altitude Impact on Heating Input Ratings
Heating input, and thus heating output, decreases with altitude. No orifice change is required up to 6,000 feet elevation and derate occurs naturally due to altitude impact. Natural gas models may require orifice change based on BTU content of gas. See Natural Gas Orifice and Altitude Tables on next page for details. For Propane Gas see the Propane Gas Conversion Table below.
Above 6,000 feet elevation orifice changes are required, and capacity reductions are a function of altitude impact and orifice change. Pressure switch change is required above 6,000 feet elevation. For Natural Gas see the Orifice and Altitude Tables on next page. For Propane Gas see the Propane Gas Conversion Table below.
NATURAL GAS DERATE CAPACITIES
WG Rated | Sea |
|
|
|
|
|
|
|
|
|
|
Input | Level | 1000 | 2000 | 3000 | 4000 | 5000 | 6000 | 7000 | 8000 | 9000 | 10,000 |
45,000 | 45,000 | 43,560 | 42,120 | 40,680 | 39,600 | 38,880 | 37,980 | 37,440 | 36,720 | 36,270 | 35,640 |
50,000 | 50,000 | 48,400 | 46,800 | 45,200 | 44,000 | 43,200 | 42,200 | 41,600 | 40,800 | 40,300 | 39,600 |
67,500 | 67,500 | 65,340 | 63,180 | 61,020 | 59,400 | 58,320 | 56,970 | 56,160 | 55,080 | 54,405 | 53,460 |
75,000 | 75,000 | 72,600 | 70,200 | 67,800 | 66,000 | 64,800 | 63,300 | 62,400 | 61,200 | 60,450 | 59,400 |
90,000 | 90,000 | 87,120 | 84,240 | 81,360 | 79,200 | 77,760 | 75,960 | 74,880 | 73,440 | 72,540 | 71,280 |
100,000 | 100,000 | 96,800 | 93,600 | 90,400 | 88,000 | 86,400 | 84,400 | 83,200 | 81,600 | 80,600 | 79,200 |
112,500 | 112,500 | 108,900 | 105,300 | 101,700 | 99,000 | 97,200 | 94,950 | 93,600 | 91,800 | 90,675 | 89,100 |
125,000 | 125,000 | 121,000 | 117,000 | 113,000 | 110,000 | 108,000 | 105,500 | 104,000 | 102,000 | 100,750 | 99,000 |
PROPANE (LP) DERATE CAPACITIES
WG Rated | Sea |
|
|
|
|
|
|
|
|
|
|
Input | Level | 1000 | 2000 | 3000 | 4000 | 5000 | 6000 | 7000 | 8000 | 9000 | 10,000 |
40,500 | 40,500 | 39,852 | 39,528 | 39,204 | 38,556 | 38,232 | 37,584 | 36,612 | 35,640 | 34,344 | 32,724 |
45,000 | 45,000 | 44,280 | 43,920 | 43,560 | 42,840 | 42,480 | 41,760 | 40,680 | 39,600 | 38,160 | 36,360 |
60,750 | 60,750 | 59,778 | 59,292 | 58,806 | 57,834 | 57,348 | 56,376 | 54,918 | 53,460 | 51,516 | 49,086 |
67,500 | 67,500 | 66,420 | 65,880 | 65,340 | 64,260 | 63,720 | 62,640 | 61,020 | 59,400 | 57,240 | 54,540 |
75,000 | 75,000 | 73,800 | 73,200 | 72,600 | 71,400 | 70,800 | 69,600 | 67,800 | 66,000 | 63,600 | 60,600 |
81,000 | 81,000 | 79,704 | 79,056 | 78,408 | 77,112 | 76,464 | 75,168 | 73,224 | 71,280 | 68,688 | 65,448 |
90,000 | 90,000 | 88,560 | 87,840 | 87,120 | 85,680 | 84,960 | 83,520 | 81,360 | 79,200 | 76,320 | 72,720 |
100,000 | 100,000 | 98,400 | 97,600 | 96,800 | 95,200 | 94,400 | 92,800 | 90,400 | 88,000 | 84,800 | 80,800 |
112,500 | 112,500 | 110,700 | 109,800 | 108,900 | 107,100 | 106,200 | 104,400 | 101,700 | 99,000 | 95,400 | 90,900 |
125,000 | 125,000 | 123,000 | 122,000 | 121,000 | 119,000 | 118,000 | 116,000 | 113,000 | 110,000 | 106,000 | 101,000 |
Gas Pressure Inches W.C.
Minimum permissible gas supply pressure for purpose of input adjustment: | Natural 4.5 | LP 11.0 |
Maximum permissible gas supply pressure for purpose of input adjustment: | Natural 11.0 | LP 13.0 |
Manifold Pressure: | Natural 3.5 | LP 10.0 |
Propane Gas Conversion Kits
PROPANE (LP) GAS
MODELS | Propane Gas Conversion Kit | Use | Use | |||
| Factory | Gas | Up to 6000 Feet | 6001 to 8000 Feet | 8001 to 10,000 Feet | |
| Heat |
| Requires Pressure | Requires Pressure | ||
| Standard |
| ||||
| Value |
| Switch Change and | Switch Change and | ||
| Input |
| ||||
| BTU/Cu. Ft. | Install Orifice | Orifice as Shown | Orifice as Shown | ||
WG3S |
| |||||
25,000 BTU | 2500 | 1.50 | 1.50 | 1.45 | ||
| ||||||
WG4S | Per Burner | Pressure Switch | Standard (.55) | Pressure Switch (.42) Included in Conversion Kit | ||
|
|
|
|
| ||
|
|
|
|
|
| |
WG5S | Optional | Gas | Up to 6000 Feet | 6001 to 8000 Feet | 8001 to 10,000 Feet | |
| 10% Field | Heat |
| Requires Pressure | Requires Pressure | |
| Converted | Value |
| Switch Change and | Switch Change and | |
| Derate | BTU/Cu. Ft. | Install Orifice | Orifice as Shown | Orifice as Shown | |
| 22,500 - 22,650 | 2500 | 1.45 | 1.45 | 1.40 | |
| BTU |
|
|
|
| |
| Pressure Switch | Standard (.55) | Pressure Switch (.42) Included in Conversion Kit | |||
| Per Burner |
All orifice sizes shown are millimeters (mm).
Form No. | |
Supersedes | |