TABLE 12
COOLING PRESSURE – (ALL TEMPERATURES °F)
| Return |
|
|
|
|
|
|
|
|
|
| |
| Air |
|
|
|
|
|
|
|
|
|
| |
Model | Temp. | Pressure | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 | |
| 75 DB | Low Side | 68 | 68 | 69 | 70 | 71 | 72 | 73 | 74 | 75 | |
| 62 WB | High Side | 215 | 228 | 242 | 256 | 272 | 289 | 305 | 324 | 343 | |
80 DB | Low Side | 73 | 73 | 74 | 75 | 76 | 77 | 78 | 79 | 80 | ||
67 WB | High Side | 220 | 234 | 248 | 263 | 279 | 296 | 313 | 332 | 352 | ||
| ||||||||||||
| 85 DB | Low Side | 76 | 76 | 77 | 78 | 79 | 80 | 81 | 82 | 83 | |
| 72 WB | High Side | 228 | 242 | 257 | 272 | 289 | 306 | 324 | 344 | 364 | |
| 75 DB | Low Side | 62 | 63 | 64 | 65 | 66 | 67 | 68 | 69 | 70 | |
| 62 WB | High Side | 214 | 230 | 247 | 265 | 280 | 299 | 316 | 333 | 351 | |
| 80 DB | Low Side | 67 | 68 | 69 | 70 | 71 | 72 | 73 | 74 | 75 | |
67 WB | High Side | 220 | 236 | 254 | 271 | 287 | 306 | 324 | 342 | 360 | ||
| 85 DB | Low Side | 72 | 73 | 74 | 75 | 76 | 77 | 78 | 79 | 80 | |
| 72 WB | High Side | 225 | 243 | 261 | 279 | 297 | 316 | 335 | 353 | 372 |
Low side pressure ± 2 psig
High side pressure ± 5 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
TABLE 13
OPTIONAL ACCESSORIES
MODELDESCRIPTION
|
|
|
Heater Package | X |
|
| |
|
|
|
|
|
Heater Package | X |
|
| |
|
|
|
|
|
Heater Package | X |
|
| |
|
|
|
|
|
Heater Package |
| X |
| |
|
|
|
|
|
Heater Package |
| X |
| |
|
|
|
|
|
Heater Package |
|
| X | |
|
|
|
|
|
Heater Package |
|
| X | |
|
|
|
|
|
Blank Off Plate | X | X | X | |
|
|
|
|
|
Barometric Fresh Air Damper | X | X | X | |
Motorized Fresh Air Damper | X | X | X | |
|
|
|
|
|
Classroom Ventilator with Exhaust | X | X | X | |
Economizer with Exhaust | X | X | X | |
|
|
|
|
|
Energy Recovery Ventilator | X | X |
| |
Energy Recovery Ventilator |
|
| X | |
|
|
|
|
|
Pull Disconnect Kit |
|
| X |
Manual