Bard WL701-C Wiring - Low Voltage Wiring, Table Operating Voltage Range, Mounting Instructions

Models: WL702-A WL701-B WL701-C

1 21
Download 21 pages 20.55 Kb
Page 9
Image 9
WIRING — LOW VOLTAGE WIRING

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

See Start-up section for information on three phase scroll compressor start-ups.

WIRING — LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TABLE 4

OPERATING VOLTAGE RANGE

TAP

RANGE

 

 

 

 

240V

253

-

216

 

 

 

 

208V

220

-

187

 

 

 

 

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

FIGURE 3

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8.

MOUNTING INSTRUCTIONS

NOTE: It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation.

MIS-1430

Manual 2100-426 Page 7

Page 9
Image 9
Bard WL701-C, WL701-B, WL702-A Wiring - Low Voltage Wiring, Table Operating Voltage Range, Mounting Instructions

FAQ

How do I lock the disconnect access door?

To lock the disconnect access door, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. A padlock may be placed through the hole in the tab preventing entry.

What is the acceptable operating voltage range for 240V and 208V taps?

For 240V, the range is 253V to 216V. For 208V, the range is 220V to 187V. The voltage should be measured at the field power connection point in the unit while the unit is operating at full load maximum amperage operating condition.

What type of thermostat cable is recommended for wiring?

A five conductor, 18 gauge, color-coded thermostat cable is recommended for wiring the Bard air conditioner.