5mm Min

 

 

 

 

450mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 8

450mm Min

For Servicing

Purposes

5mm Min

In Operation

Fig. 9

20mm/5mm Min

See * NOTE:

200mm Min

780mm

200mm Min

7.0Site Requirements

7.1Location

1.The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard-see Section 7.3).

2.If the boiler is sited in an unheated enclosure then it is recommended to leave the ON/OFF Selector Switch in the domestic hot water and central heating position to give frost protection.

3.If the boiler is fitted in a room containing a bath or shower reference must be made to the relevant requirements.

In GB this is the current I.E.E. Wiring Regulations and Building Regulations.

In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and the current ETCI rules.

4.If the boiler is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).

7.2Clearances (Figs. 8 & 9)

1.A flat vertical area is required for the installation of the boiler.

2.These dimensions include the necessary clearances around the boiler for case removal, access during routine maintenance and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.

* NOTE: The boiler can be operated with a clearance of 5mm at the right. This is also sufficient for routine maintenance. However a clearance of 20mm is required if it is necessary to remove the secondary heat exchanger. This should be considered when siting the appliance and in the event of any subsequent alteration in the area of installation.

14© Baxi Heating UK Ltd 2007

Page 14
Image 14
Baxi Potterton 30 HE manual Site Requirements, Location, Clearances Figs

30 HE specifications

The Baxi Potterton 30 HE is a popular choice among homeowners seeking an efficient and reliable boiler solution. Recognized for its compact design and advanced technologies, this boiler is ideal for various residential heating needs.

One of the standout features of the Baxi Potterton 30 HE is its high efficiency rating, which ensures lower energy consumption and reduced utility bills. With an impressive efficiency of up to 90%, this boiler operates at a much higher capacity compared to older models, making it both environmentally friendly and cost-effective. The 30 HE is particularly well-suited for medium to larger homes with a higher demand for hot water.

The Baxi Potterton 30 HE incorporates a range of innovative technologies aimed at enhancing performance and reliability. The automatic modulation function adjusts the boiler's output according to demand, ensuring that it only works as hard as necessary. This not only prolongs the lifespan of the unit but also maximizes comfort levels in the home.

Another feature of the 30 HE is its low noise operation. This boiler has been specifically designed to minimize sound, allowing it to operate quietly in the background without disturbing daily activities. This makes it an ideal choice for homes where noise can be a concern, particularly in open-plan living spaces.

The compact dimensions of the Baxi Potterton 30 HE make it easy to install in various locations, whether it be in a kitchen, utility room, or even a loft space. Its lightweight construction further simplifies the installation process, saving both time and labor costs.

In terms of user-friendliness, the boiler is equipped with an intuitive control panel that allows homeowners to easily adjust settings and monitor performance. This user-centric design ensures that even those who may not be technically inclined can manage their heating requirements with ease.

Safety features are also a priority in the design of the Baxi Potterton 30 HE. It includes built-in safety mechanisms such as frost protection and a burner pressure monitoring system, which work to prevent overheating and ensure optimal operation.

Overall, the Baxi Potterton 30 HE is an efficient, reliable, and user-friendly boiler that meets the heating demands of modern homes. Its blend of advanced technologies, compact size, and focus on safety make it a standout choice for homeowners seeking a high-performance heating solution.