Baxi Potterton 30 HE manual External termination via internal, Condensate Drain

Models: 30 HE

1 56
Download 56 pages 38.59 Kb
Page 16
Image 16

Termination to an internal soil and vent pipe

Boiler

 

50mm

per

metre

 

 

 

 

 

 

 

 

2.5°

 

 

of

pipe

 

Minimum

 

 

 

run

 

 

fall

 

 

 

 

 

 

 

 

 

 

 

450mm min

 

 

 

 

 

External termination via internal

 

Boiler

 

 

 

 

 

discharge branch

 

 

 

 

 

 

e.g sink waste - downstream

Sink

50mm

per

 

 

 

Pipe must terminate

metre

 

 

above water level but

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

 

below surrounding

 

2.

 

 

 

 

pipe

run

 

 

 

 

 

 

surface

 

Minimum

 

 

 

 

 

 

 

fall

 

 

 

External termination to a drain or gully

Boiler

Pipe must terminate above water level but below surrounding surface

50mm

per

 

 

 

metre

 

 

 

of

 

 

 

pipe

2.5°

Minimum

run

 

 

 

 

 

 

fall

 

External termination to a purpose made soak-away

Boiler

50mm

per

 

 

 

 

 

 

 

500mm min

 

 

 

 

 

 

 

 

 

 

 

 

Holes in the soak-away must

 

 

metre

of

 

 

 

 

 

 

 

 

pipe

 

 

 

 

2.5°

Minimum

run

 

 

face away from the building

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.0Site Requirements

7.6Condensate Drain

FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER

The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run.

1.The condensate outlet terminates in a 1” BSP nut and seal for the connection of 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.

2.Ensure the discharge of condensate complies with any national or local regulations in force.

BS 6798:2000 & Part H1 of the Building Regulations give further guidance.

3.The discharge pipe should be run in a proprietary drain pipe material e.g. PVC, PVC-U, ABS, PVC-C or PP.

4.Metal pipework is NOT suitable for use in condensate discharge systems.

5.The pipe should be a minimum of 21.5mm diameter and must be supported using suitably spaced clips to prevent sagging.

6.It is advisable to keep the condensate pipe internal.

7.External runs greater than 3 metres or runs in cold areas should use 32mm waste pipe.

8.If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run.

9.In all cases discharge pipe must be installed to aid disposal of the condensate. To reduce the risk of condensate being trapped, as few bends and fittings as possible should be used.

10.When discharging condensate into a soil stack or waste

pipe the effects of existing plumbing must be considered. If soil pipes or waste pipes are subjected to internal pressure fluctuations when WC's are flushed or sinks emptied then back-pressure may force water out of the boiler trap and cause appliance lockout.

Examples are shown of the following methods of termination:-

i)to an internal soil & vent pipe

ii)via an internal discharge branch (e.g. sink waste)

iii)to a drain or gully

iv)to a purpose made soakaway

16© Baxi Heating UK Ltd 2007

Page 16
Image 16
Baxi Potterton 30 HE manual External termination via internal, Condensate Drain