Termination to an internal soil and vent pipe
Boiler
| 50mm | per | metre |
| ||
|
|
| ||||
|
|
|
| |||
2.5° |
|
| of | pipe | ||
| Minimum |
|
|
| run | |
|
| fall |
|
|
|
|
|
|
|
|
|
|
|
450mm min
|
|
|
|
| External termination via internal | |||
| Boiler |
|
|
|
|
| discharge branch | |
|
|
|
|
|
| e.g sink waste - downstream | ||
Sink | 50mm | per |
|
|
| Pipe must terminate | ||
metre |
|
| above water level but | |||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
| of |
| below surrounding | |
| 2. |
|
|
|
| pipe | run | |
|
|
|
|
|
| surface | ||
| 5° | Minimum |
|
| ||||
|
|
|
|
| fall |
|
|
|
External termination to a drain or gully
Boiler
Pipe must terminate above water level but below surrounding surface
50mm | per |
| |
|
| metre |
|
|
| of |
|
|
| pipe | |
2.5° | Minimum | run | |
| |||
|
|
| |
|
| fall |
|
External termination to a purpose made
Boiler
50mm | per |
|
|
|
|
|
|
| 500mm min | |
|
|
|
|
|
| |||||
|
|
|
|
|
| Holes in the | ||||
|
| metre | of |
|
|
|
|
| ||
|
|
| pipe |
|
|
|
| |||
2.5° | Minimum | run |
|
| face away from the building | |||||
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||
|
|
| fall |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7.0Site Requirements
7.6Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run.
1.The condensate outlet terminates in a 1” BSP nut and seal for the connection of 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
2.Ensure the discharge of condensate complies with any national or local regulations in force.
BS 6798:2000 & Part H1 of the Building Regulations give further guidance.
3.The discharge pipe should be run in a proprietary drain pipe material e.g. PVC,
4.Metal pipework is NOT suitable for use in condensate discharge systems.
5.The pipe should be a minimum of 21.5mm diameter and must be supported using suitably spaced clips to prevent sagging.
6.It is advisable to keep the condensate pipe internal.
7.External runs greater than 3 metres or runs in cold areas should use 32mm waste pipe.
8.If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run.
9.In all cases discharge pipe must be installed to aid disposal of the condensate. To reduce the risk of condensate being trapped, as few bends and fittings as possible should be used.
10.When discharging condensate into a soil stack or waste
pipe the effects of existing plumbing must be considered. If soil pipes or waste pipes are subjected to internal pressure fluctuations when WC's are flushed or sinks emptied then
Examples are shown of the following methods of termination:-
i)to an internal soil & vent pipe
ii)via an internal discharge branch (e.g. sink waste)
iii)to a drain or gully
iv)to a purpose made soakaway
16© Baxi Heating UK Ltd 2007