Domestic Hot Water - Follow operational sequence
16.0Fault Finding
Turn selector to
neon illuminated
YES
Turn thermostat to max.
Open DHW tap fully. DHW
flow switch operated
YES![](/images/new-backgrounds/1056868/5686897xi3.webp)
Primary water is diverted from CH system to DHW heat exchanger and flow microswitch operated neon illuminated
YES ![](/images/new-backgrounds/1056868/5686897xi5.webp)
Pump runs
YES![](/images/new-backgrounds/1056868/5686897xi6.webp)
Primary flow switch operated
YES![](/images/new-backgrounds/1056868/5686897xi7.webp)
Fan runs at max speed
YES
NO
NO
NO
NO
NO
NO
Go to section ‘A’ |
| |||
|
| |||
|
| |||
Is mains water | YES | |||
filter and differential | ||||
| ||||
| ||||
assembly clean? |
| |||
|
|
|
| |
YES |
|
|
| |
|
| |||
|
|
|
| |
DHW flow rate more than |
| |||
2.5l/min. |
| |||
|
|
| NO | |
|
|
| ||
Continuity across DHW flow | ||||
microswitch terminals and |
| |||
PCB - A5 connector | YES | |||
terminals 5 & 6 |
| |||
| ||||
|
|
|
| |
|
| |||
neon flashing |
| |||
Go to section ‘B’ |
| |||
|
| |||
|
| |||
neon flashing |
| |||
Go to section ‘C’ |
| |||
|
|
| YES | |
|
|
| ||
neon flashing | ||||
| ||||
|
|
|
| |
|
| NO |
| |
|
|
| ||
|
|
| ||
| neons flashing |
| ||
Go to section ‘D’ |
| |||
|
|
|
|
Replace diaphragm
YES ![](/images/new-backgrounds/1056868/5686897xi8.webp)
DHW flow valve diaphragm
damaged
NO
DHW flow valve rod
obstructed
Replace DHW flow
microswitch
Replace PCB
Turn selector to reset
position. If regular resetting is
required or appliance still
does not operate
investigation is necessary
Go to sections ‘J’ & ‘M’
Air pressure switch proved
YES![](/images/new-backgrounds/1056868/5686897xi10.webp)
Spark at ignition electrodes
for up to 10 seconds
YES
Burner on neon
illuminated
YES![](/images/new-backgrounds/1056868/5686897xi12.webp)
Burner extinguishes
after 10 seconds
NO
Burner output modulates to maintain temperature set at thermostat
YES![](/images/new-backgrounds/1056868/5686897xi13.webp)
Close DHW tap
YES![](/images/new-backgrounds/1056868/5686897xi14.webp)
DHW flow valve
senses no flow.
Primary water diverted to CH system. DHW flow switch released off
YES![](/images/new-backgrounds/1056868/5686897xi15.webp)
Burner goes out
NO
NO
NO
YES
NO
NO
NO
neon flashing
Go to section ‘E’
YES neon flashing
NO
Replace PCB
Go to section ‘F’
neon flashing
Go to sections ‘I’ & ‘L’
Reduce the DHW flow rate. If burner does not modulate clean DHW temperature sensor and DHW heat exchanger. If modulation does not occur go to section ‘G’
Diverter valve spindle
assembly faulty
YES
Fan stops
Turn the selector to the reset position. If the light does not extinguish go to section H &
K
Pump stops | YES |
Operation sequence correct |