Baxi Potterton 30 HE manual Checking the Burner Pressure, Pressure Test Point Sealing Screw

Models: 30 HE

1 56
Download 56 pages 38.59 Kb
Page 33
Image 33

Pressure Test Point

Sealing Screw

OUT

MIN

Gas Valve

 

Fig. 48

Plastic

Protection

Cap

Modulator

Wire

Maximum Rate

Adjustment Nut

Minimum Rate

Adjustment Nut

Fig. 49 NOTE: Gas Valve Electrical

Plug/Igniter not shown for clarity.

2

3

0

4

bar

Selector Switch

Pressure Gauge

Fig. 50

 

2

Reset

 

1

3

0

4

 

bar

Power On

Neon

Central Heating

Hot Water

 

 

Temperature Control

Temperature Control

Fig. 51

11.0 Commissioning the Boiler

11.2Checking the Burner Pressure

1.Turn on the gas and electrical supplies to the boiler and ensure that all external controls are calling for heat.

2.Set the temperature controls to maximum and the selector switch to the Off position (Fig. 51).

3.Slacken the pressure test point sealing screw on the gas valve and connect a pressure gauge (Fig. 48).

4.Undo the screws securing the inner door panel. Lift the panel slightly to disengage it from the studs on top of the case.

5.Turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 2 seconds to reset the boiler (Fig. 51).

6.Turn the selector switch to the Cental Heating and

Domestic Hot Water position ( ). The power On neon ( ) will illuminate (Fig. 51).

7.Turn a hot water tap on to give a flow rate of at least 10l/min.

8.The pressure should be :-

NG 12.1mbar

Propane 32.3mbar

If not, check that the gas supply pressure is correct (Natural Gas 20mbar, and Propane 37mbar).

9.The pressure can be adjusted if required.

10.To check and set minimum pressure first remove one of the modulator wires.

Adjusting the Pressure (Fig 49)

11.Remove the plastic protection cap from the pressure adjustment nuts on the valve.

12.The smaller nut (5mm) adjusts minimum pressure and the larger nut (8mm) maximum pressure.

13.Using a suitable spanner adjust the relevant nut until the correct pressure is achieved.

14.Once the pressure has been set turn the boiler off and disconnect the pressure gauge.

15.Tighten the pressure test screw and refit the modulator to the valve. Reassemble in reverse order.