Instruction Manual – Model CF500/CF800 Oil Burner
Wire the burner — R8184 (alternate)
Install the burner and all wiring in accordance with the National Electrical Code and all applicable local codes or requirements.
Wire the burner in compliance with all instructions provided by the appliance manufacturer. Verify operation of all controls in accordance with the appliance manufacturer's guidelines.
See Figure 9b for an alternate wiring diagram, with R8184 oil primary, for reference purposes only.
Do not
Electrical shock hazard - can cause injury or death. Disconnect power before installing or servicing. Provide ground wiring to the burner in accordance with the National Electrical Code.
Figure 9b – Alternate wiring R8184
Sequence of operation — typical
1.Standby — The burner is idle, waiting for a call for heat.
2.Trial for ignition (TFI) — The fuel valve is opened, as applicable. A flame should be established within the 15- second lockout time
3.Lockout — If flame is not sensed by the end of the TFI, the control shuts down on safety lockout and must be manually reset.
•To reset the control after lockout, wait 2 to 3 minutes after lockout to give the internal switch time to cool.
•Then push the reset button on the primary control, allowing the burner to operate in normal sequence.
•Troubleshoot the reason for the flame sense failure.
4.Run — The burner runs until the call for heat is satisfied.
1
Standby
2 | Trial for | 3 |
| Lockout | |
| ignition | |
|
| |
4 |
|
|
| Run |
|
Legend
FD Fused disconnect, by others LM Limit controls, by others
O P Operating controls, by others PR Oil primary control, R8184 typical
CCFlame sensor, cad cell typical
TR Ignition transformer M1 Burner motor
S1 Oil valve
Form 6104 | 11 |