12 Form 6104 BCF5-R0301
Instruction Manual – Model CF500/CF800 Oil Burner

Z dimension

Should be set per these instructions (see page 7). The acorn
nut (Figure 6, item c, page 7) should never be loosened
once the Z dimension is initially set.

Initial head position

The indicator plate assembly markings correspond to head
position settings.
Loosen the fastener (Figure 6, item d, page 7) and slide
the indicator plate until the number on the plate corre-
sponds to the initial head setting given in Table 4 for the
desired firing rate.
When the head position has been set, tighten the fastener
and spline nut.

Initial air settings

Loosen the air band and shutter, and adjust to the settings
for the applicable firing rate shown in Table 5.
These initial settings should be adequate for starting the
burner. Once the burner is in operation, the air settings will
Table 4 – Initial indicator adjustment plate settings
(head position)
Prepare the burner for start-up
Start-up checklistVerify the following
before attempting to start burner.
Combustion air supply and venting have been inspected
and verified to be free of obstructions and installed in
accordance with all applicable codes.
Oil nozzle has been selected correctly and securely installed
in the nozzle adapter.
Fuel unit by-pass plug has not been installed for one-pipe
oil system.
By-pass plug has been installed for two-pipe oil system.
Fuel connection to nozzle line assembly is secure.
Dimension Z has been set per this instruction manual.
Fuel supply line is correctly installed, the oil tank is
sufficiently filled, and shut-off valves are open.
Burner is securely mounted in appliance, with pressure
firing plate and gasket installed for pressurized chamber
application.
Appliance has been filled with water (boilers) and controls
have been operationally checked.
Burner has been installed in accordance with appliance
manufacturer’s instructions (when available).
Also refer to appliance manufacturer’s instructions (when
available) for start-up procedures.
Table 5 – Initial air settings
Rate
GPH
Approximate air settings
CF500 CF800
Tube ATube B
Shutter Band Shutter Band Shutter Band
1.75 1 0 -- -- -- --
2.25 2 0 -- -- -- --
3.00 10 1 1 0 -- --
3.50 10 2 3 0 -- --
4.00 10 3 4 0 -- --
5.00 10 5 9 0 8 2
5.50 10 10 9 5 9 4
6.00 -- -- 10 310 3
7.00 -- -- 10 810 5
8.00 -- -- -- -- 10 10
be adjusted for best performance as discussed later in this
manual.
Follow the procedures given later in this manual for fine-
tuning the air settings.

Set appliance limit controls

Set the appliance limit controls in accordance with the
appliance manufacturer's recommendations.

Prepare the fuel unit for air venting

To vent air from one-pipe oil systems, attach a clear hose to
the vent plug on the fuel unit. Provide a container to catch
the oil. Loosen the vent plug.
Vent the air as described under Start the burner, page 13,
when using the R7184 control.
Rate
GPH
Approximate head settings
CF500 CF800
Tube ATube B
1.75 0----
2.25 0
3.00 40--
3.50 5 1 --
4.00 5 2 --
5.00 6 4 3
5.50 6 4 4
6.00 -- 4 4
7.00 -- 6 5
8.00 -- -- 6