Beckett CG10(A) setup guide Weil McLain 88 Series, Commercial Gas Burner OEM Setup Guide

Models: CG10(A)

1 12
Download 12 pages 12.1 Kb
Page 11
Image 11
Weil McLain 88 Series 2

Commercial Gas Burner OEM Setup Guide

Weil McLain 88 Series 2

 

Boiler

Burner

Firing Mode

Rate

Manifold

Head Type

Damper

Shutter

Air Tube

 

 

 

 

 

MBH

Pressure

/ Head

Setting

Band

Insertion

 

 

 

 

 

 

in. water

Setting

Blue / Red

Settings

Inches

 

 

488

CG10

Low Fire Start

986

1.5

/ 4.5

10.6S / 10.6

-

10/4

4.00"

 

 

588

CG25

Mod

676 / 1357

0.8

/ 3.5

25.1S / 25.1

16 / 41

-

4.00"

 

 

688

CG25

Mod

784 / 1729

0.8

/ 3.7

25.2S / 25.2

22 / 53

-

4.00"

 

 

788

CG50

Mod

904 / 2017

0.6

/ 3.1

50.1S / 50.1

19 / 32

-

4.00"

 

 

888

CG50

Mod

1030 / 2396

0.5 / 3.05

50.2S / 50.2

20 / 39

-

4.00"

 

 

988

CG50

Mod

1055 / 2666

0.6 / 3.75

50.2S / 50.2

20 / 43

-

4.00"

 

 

1088

CG50

Mod

1228 / 3089

0.55

/ 3.65

50.3S / 50.3

21 / 48

-

4.00"

 

 

1188

CG50

Mod

1458 / 3403

0.6

/ 3.6

50.4S / 50.4

23 / 53

-

4.00"

 

 

1288

CG50

Mod

1462 / 3762

0.6 / 4.15

50.4S / 50.4

23 / 75

-

4.00"

 

 

1388

CG50

Mod

1719 / 4171

0.65 / 4.0

50.5S / 50.5

26 / 70

-

4.00"

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 11
Image 11