Beckett CG10(A) setup guide Burnham MPC, Commercial Gas Burner OEM Setup Guide

Models: CG10(A)

1 12
Download 12 pages 12.1 Kb
Page 4
Image 4
Burnham MPC

Commercial Gas Burner OEM Setup Guide

Burnham MPC

 

Boiler

Burner

Firing Mode

Rate

Manifold

Head Type

Damper

Shutter

Air Tube

 

 

 

 

 

MBH

Pressure

/ Head

Setting

Band

Insertion

 

 

 

 

 

 

 

in. water

Setting

Blue / Red

Settings

Inches

 

 

MPC 4

CG10

Low Fire Start

500

1.0

/ 1.8

10.3 / 10.3

-

6/0

4.25"

 

 

MPC 5

CG10

Low Fire Start

773

1.6

/ 3.2

10.5S / 10.4

-

10/0

4.25"

 

 

MPC 6

CG15

Mod

540

/ 995

1.15

/ 3.15

15.2S / 15.2

26 / 45

-

4.25"

 

 

MPC 7

CG15

Mod

628 / 1216

1.1

/ 3.6

15.3S / 15.3

29 / 60

-

4.25"

 

 

MPC 8

CG15

Mod

668 / 1438

1.1

/ 3.6

25.1S / 25.1

16 / 45

-

4.25"

 

 

MPC 9

CG25

Mod

772 / 1660

0.8 / 3.57

25.2S / 25.2

22 / 48

-

4.25"

 

 

MPC10

CG25

Mod

878 / 1881

0.75 / 3.4

25.3S / 25.3

25 / 54

-

4.25"

 

 

MPC11

CG25

Mod

1052

/ 2103

0.9

/ 3.6

25.4S / 25.4

27 / 62

-

4.25"

 

 

MPC12

CG25

Mod

1048

/ 2325

0.9

/ 4.2

25.4S / 25.4

29 / 83

-

4.25"

 

 

MPC13

CG50

Mod

1048

/ 2325

0.8

/ 3.6

50.2S / 50.2

20 / 39

-

4.25"

 

 

MPC14

CG50

Mod

1247

/ 2769

0.7

/ 3.4

50.3S / 50.3

22 / 43

-

4.25"

 

 

MPC15

CG50

Mod

1216

/ 2991

0.7

/ 4.0

50.3S / 50.3

22 / 50

-

4.25"

 

 

MPC16

CG50

Mod

1214

/ 3213

0.7

/ 4.3

50.3S / 50.3

21 / 70

-

4.25"

 

 

MPC17

CG50

Mod

1471

/ 3435

0.7

/ 4.0

50.4S / 50.4

24 / 60

-

4.25"

 

 

MPC18

CG50

Mod

1389

/ 3657

0.7

/ 4.9

50.4S / 50.4

25 / 72

-

4.25"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burnham V11

 

Boiler

Burner

Firing Mode

Rate

Manifold

Head Type

Damper

Shutter

Air Tube

 

 

 

 

 

MBH

Pressure

/ Head

Setting

Band

Insertion

 

 

 

 

 

 

 

in. water

Setting

Blue / Red

Settings

Inches

 

 

V1104

CG10

Low Fire Start

843

1.0

/ 3.3

10.6S / 10.6

-

10 / 0

4.00"

 

 

V1104

CG15

Mod

478

/ 845

1.1 / 3.45

15.1S / 15.1

22 / 42

 

4.00"

 

 

V1105

CG10

Low Fire Start

1070

1.0 / 4.75

10.6S / 10.6

-

10 / 5

4.00"

 

 

V1105

CG15

Mod

554 / 1078

0.9

/ 3.8

15.2S / 15.2

25 / 50

-

4.00"

 

 

V1106

CG15

Mod

757 / 1343

1.15 / 3.3

15.4S / 15.4

33 / 67

-

4.00"

 

 

V1106

CG25

Mod

670 / 1340

0.8

/ 3.1

25.1S / 25.1

15 / 40

-

4.00"

 

 

V1107

CG25

Mod

782 / 1588

0.75 / 3.1

25.2S / 25.2

21 / 46

-

4.00"

 

 

V1108

CG25

Mod

896 / 1876

0.77

/ 3.36

25.3S / 25.3

27 / 55

-

4.00"

 

 

V1109

CG25

Mod

1037

/ 2136

0.78

/ 3.32

25.4S / 25.4

28 / 62

-

4.00"

 

 

V1110

CG25

Mod

1200

/ 2396

0.74

/ 2.94

25.5S / 25.5

32 / 95

-

4.00"

 

 

V1111

CG50

Mod

1052

/ 2710

0.55

/ 3.55

50.2S / 50.2

20 / 42

-

4.00"

 

 

V1112

CG50

Mod

1238

/ 2915

0.55 / 2.9

50.3S / 50.3

21 / 42

-

4.00"

 

 

V1113

CG50

Mod

1228

/ 3103

0.53 / 3.4

50.3S / 50.3

21 / 50

-

4.00"

 

 

V1114

CG50

Mod

1443

/ 3392

0.54

/ 2.97

50.4S / 50.4

23 / 50

-

4.00"

 

 

V1115

CG50

Mod

1443

/ 3680

0.54 / 3.4

50.4S / 50.4

23 / 70

-

4.00"

 

 

V1116

CG50

Mod

1700

/ 3897

0.57 / 3.0

50.5S / 50.5

26 / 65

-

4.00"

 

 

V1117

CG50

Mod

1700

/ 4186

0.57

/ 3.44

50.5S / 50.5

26 / 75

-

4.00"

 

 

V1118

CG50

Mod

1700

/ 4474

0.56

/ 3.85

50.5S / 50.5

26 / 85

-

4.00"

 

 

V1119

CG50

Mod

1703

/ 4713

0.57

/ 4.15

50.5S / 50.5

26 / 95

-

4.00"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 4