Commercial Gas Burner OEM Setup Guide
Armstrong LG-14
| Boiler | Burner | Firing Mode | Rate | Manifold | Head Type | Damper | Shutter | Air Tube |
|
|
|
|
| MBH | Pressure | / Head | Setting | Band | Insertion |
|
|
|
|
|
| in. water | Setting | Blue / Red | Settings | Inches |
|
| 280 LP | CG10 | On/Off | 282 | 1.9 | 10.1S / 10.1 | - | 1.5 / 0 | 2.25" |
|
| 280 Nat | CG10 | On/Off | 284 | 2.2 | 10.1S / 10.1 | - | 1.5 / 0 | 2.25" |
|
| 350 LP | CG10 | On/Off | 350 | 2.9 | 10.1S / 10.1 | - | 2.5 / 0 | 2.25" |
|
| 350 Nat | CG10 | On/Off | 351 | 3.4 | 10.1S / 10.1 | - | 3 / 0 | 2.25" |
|
| 420 LP | CG10 | On/Off | 422 | 1.3 | 10.3S / 10.3 | - | 4 / 0 | 2.25" |
|
| 420 Nat | CG10 | On/Off | 419 | 1.2 | 10.3S / 10.3 | - | 3.5 / 0 | 2.25" |
|
| 500 LP | CG10 | On/Off | 498 | 1.8 | 10.3S / 10.3 | - | 6.5 / 0 | 2.25" |
|
| 500 Nat | CG10 | On/Off | 499 | 1.7 | 10.3S / 10.3 | - | 5.5 / 0 | 2.25" |
|
|
|
|
|
|
|
|
|
|
|
|