Commercial Gas Burner OEM Setup Guide
Peerless LC/LCE
| Boiler | Burner | Firing Mode | Rate | Manifold | Head Type | Damper | Shutter | Air Tube |
| ||
|
|
|
| MBH | Pressure | / Head | Setting | Band | Insertion |
| ||
|
|
|
|
|
| in. water | Setting | Blue / Red | Settings | Inches |
| |
| LC04 | CG10 | Low Fire Start | 691 | 1.4 | / 3.2 | 10.5S / 10.4 | - | 7.5 / 0 | 3.00" |
| |
| LC05 | CG15 | Low/High | 468 | / 881 | 0.8 | / 2.9 | 15.2S / 15.1 | 25 / 40 | - | 3.00" |
|
| LC05R | CG15 | Low/High | 476 | / 806 | 0.9 / 2.35 | 15.2S / 15.1 | 25 / 37 | - | 3.00" |
| |
| LC06 | CG15 | Low/High | 550 / 1086 | 0.9 | / 3.9 | 15.2S / 15.2 | 25 / 52 | - | 3.00" |
| |
| LC07 | CG15 | Low/High | 641 / 1270 | 0.8 / 3.65 | 15.3S / 15.4 | 33 / 59 | - | 3.00" |
| ||
| LC07 | CG25 | Mod | 659 / 1280 | 0.7 | / 3.0 | 25.1S / 25.1 | 16 / 38 | - | 3.00" |
| |
| LC08 | CG25 | Mod | 669 / 1469 | 0.7 | / 3.4 | 25.1S / 25.1 | 16 / 43 | - | 3.00" |
| |
| LC09 | CG25 | Mod | 774 / 1664 | 0.7 | / 3.4 | 25.2S / 25.2 | 21 / 49 | - | 3.00" |
| |
| LC10 | CG25 | Mod | 896 / 1860 | 0.8 | / 3.1 | 25.3S / 25.3 | 25 / 52 | - | 3.00" |
| |
| LC11 | CG25 | Mod | 1037 | / 2059 | 0.7 | / 3.1 | 25.4S / 25.4 | 28 / 60 | - | 3.00" |
|
| LC12 | CG25 | Mod | 1184 | / 2278 | 0.7 | / 2.9 | 25.5S / 25.5 | 32 / 68 | - | 3.00" |
|
| LCE13 | CG50 | Mod | 1060 | / 2460 | 0.55 / 2.7 | 50.2S / 50.2 | 20 / 40 | - | 3.00" |
| |
| LCE14 | CG50 | Mod | 1044 | / 2657 | 0.5 | / 3.5 | 50.2S / 50.2 | 20 / 42 | - | 3.00" |
|
| LCE15 | CG50 | Mod | 1228 | / 2850 | 0.5 | / 2.9 | 50.3S / 50.3 | 21 / 42 | - | 3.00" |
|
| LCE16 | CG50 | Mod | 1228 | / 3043 | 0.5 | / 3.2 | 50.3S / 50.3 | 21 / 49 | - | 3.00" |
|
| LCE17 | CG50 | Mod | 1228 | / 3236 | 0.5 | / 3.5 | 50.3S / 50.3 | 21 / 70 | - | 3.00" |
|
| LCE18 | CG50 | Mod | 1439 | / 3451 | 0.55 | / 3.05 | 50.4S / 50.4 | 23 / 50 | - | 3.00" |
|
| LCE19 | CG50 | Mod | 1443 | / 3622 | 0.5 | / 3.2 | 50.4S / 50.4 | 23 / 60 | - | 3.00" |
|
| LCE20 | CG50 | Mod | 1443 | / 3815 | 0.5 | / 3.7 | 50.4S / 50.4 | 23 / 75 | - | 3.00" |
|
| LCE21 | CG50 | Mod | 1700 | / 4027 | 0.5 | / 3.1 | 50.5S / 50.5 | 26 / 75 | - | 3.00" |
|
| LCE22 | CG50 | Mod | 1700 | / 4239 | 0.5 | / 3.3 | 50.5S / 50.5 | 26 / 78 | - | 3.00" |
|
| LCE23 | CG50 | Low/High | 2197 | / 4450 | 0.75 / 3.8 | 50.5S /50.5 | 33 / 82 | - | 3.00" |
| |
| LCE23 | CG50 | Mod | 1707 | / 4450 | 0.55 / 3.8 | 50.5S / 50.5 | 26 / 82 | - | 3.00" |
|
Peerless SC/SCT
| Boiler | Burner | Firing Mode | Rate | Manifold | Head Type | Damper | Shutter | Air Tube |
|
|
|
|
| MBH | Pressure | / Head | Setting | Band | Insertion |
|
|
|
|
|
| in. water | Setting | Blue / Red | Settings | Inches |
|
| SC05 | CG10 | Low Fire Start | 444 | 1.0 / 3.0 | 10.1 / 10.1 | - | 10 / 2 | 2.50" |
|
| SC06 | CG10 | On/Off | 491 | 2.0 | 10.3 / 10.3 | - | 5 / 0 | 2.50" |
|
| SC07 | CG10 | On/Off | 569 | 2.7 | 10.3 / 10.3 | - | 8 / 0 | 2.50" |
|
| SC08 | CG10 | Low Fire Start | 656 | 1.5 / 3.4 | 10.4S / 10.4 | - | 6.5 / 0 | 2.50" |
|
| SC09 | CG10 | Low Fire Start | 741 | 2.0 / 4.2 | 10.4S / 10.4 | - | 8.5 / 0 | 2.50" |
|
| SC10 | CG10 | Low Fire Start | 802 | 2.0 / 3.9 | 10.5S /10.5 | - | 10 / 3 | 2.50" |
|