Beckett SL7175, SLD375, SL5125, SLD4100 Preliminary Burner Settings, Control Circuit Safety Checks

Models: SL6150 SL4100 SL7175 SL375 SLD5125 SLD4100 SL5125 SLD375

1 32
Download 32 pages 25.29 Kb
Page 21
Image 21

21

2.Direct vented – Take a draft reading from the inspection port of the boiler. This over-fire reading will be a positive pressure. Approximate over- fire draft readings can be found in the burner settings table.

3.Pump pressure – Install a pump pressure gauge in the oil pump following the oil burner manufacturer’s recommendations. Adjust the pump pressure as per the preliminary burner settings.

4.Combustion Set-up – The air settings shown in the table are approximate. The burner must be adjusted during actual field installed conditions. Failure to do so will result in poor boiler performance and nuisance service calls. After proper draft and oil pressure have been established:

a.Begin to close the air band to create a slight trace of smoke as noted on the Bacharach or equivalent smoke tester scale.

b.Take a flue gas sample and note the CO2 reading. It will be about 13% to 14%

c.Open the air band to reduce the CO2 approximately 2%.

d.Check for “0” smoke. Head settings and/or air band may be altered to obtain the above results. Lock the air band and head setting screws in place.

The above procedure will give a built in margin to ensure clean operation throughout the heating season. Should draft conditions vary, lint accumulate in the fan, heavier oil delivered, or other adverse conditions be encountered you will have a reasonable margin of built in protection before smoke generation begins.

Preliminary Burner Settings

Boiler

Burner

Nozzle

Air

Turbulator/

Pump Press

CO2

Draft

Smoke

 

 

 

Setting

Head

 

 

Overfire

 

SL375

Riello F5

.65x80oB

2.50

0.5

150 PSI

11.0%

+.02

#0

 

Beckett AFG

.60x70oB

6/0

N/A

160 PSI

11.4%

+.02

#0

 

Beckett NX

.60x60oB

N/A

1.50

160 PSI

11.0%

+.02

#0

 

HeatWise P1

.60x60oA

8.00

4.0

150 PSI

11.0%

+.02

#0

SLD375

Riello BF5

.65x80oB

3.25

0.5

150 PSI

11.0%

+.05

#0

 

Beckett NX

.60x60oB

N/A

1.50

160 PSI

12.0%

+.05

#0

SL4100

Riello F5

.85x80oB

3.25

0.5

150 PSI

11.0%

+.04

#0

 

Beckett AFG

.75x60oB

7/1

N/A

160 PSI

11.3%

+.04

#0

 

Beckett NX

.85x60oB

N/A

3.00

140 PSI

11.0%

+.04

#0

 

HeatWise P2

.85x80oB

7.50

4.0

150 PSI

10.5%

+.04

#0

SLD4100

Riello BF5

.85x80oB

4.75

1.0

150 PSI

11.0%

+.08

#0

 

Beckett NX

.85x60oB

N/A

3.00

140 PSI

11.0%

+.08

#0

SL5125

Riello F5

1.00x80oB

3.00

4.0

150 PSI

11.0%

+.07

#0

 

HeatWise P2

1.00x80oB

4.00

6.0

160 PSI

10.5%

+.07

#0

 

Beckett NX

1.00x60oB

N/A

4.00

150 PSI

11.0%

+.07

#0

SLD5125

Riello BF5

1.00x80oB

4.75

4.0

150 PSI

11.0%

+.11

#0

 

Beckett NX

1.00x60oB

N/A

4.00

150 PSI

11.5%

+.11

#0

SL6150

Riello F5

1.25x80oB

5.75

4.0

150PSI

11.0%

+.09

#0

 

Beckett NX

1.25x45oB

N/A

2.00

140 PSI

11.1%

+.09

#0

 

HeatWise P2

1.25x70oB

5.50

8.0

150 PSI

11.5%

+.09

#0

SL7175

HeatWise P2

1.75x70oB

8.00

12.0

100PSI

12.0%

+.11

#0

 

Beckett NX

1.35x45oB

N/A

3.00

150 PSI

12.0%

+.11

#0

Control Circuit Safety Checks

Check the safety controls on the boiler after completing the oil burner adjustments. A safety control check for satisfactory performance must be performed.

Page 21
Image 21
Beckett SL7175, SLD375, SL5125, SLD4100, SLD5125, SL375, SL4100 manual Preliminary Burner Settings, Control Circuit Safety Checks