SNMP Trap Number:
Variable | Trap No. | Description |
dupsCommunicationLost | 1 | SEVER: Communication with the UPS failed |
dupsCommunicationEstablished | 2 | INFORMATION: Communication with the UPS reestablished |
dupsPowerFail | 3 | WARNING: Power failed! The UPS is operating on battery power |
dupsPowerRestored | 4 | INFORMATION: Power restored! The utility power restored |
dupsLowBattery | 5 | SEVER: The UPS batteries are low and will soon be exhausted |
dupsReturnFromLowBattery | 6 | INFORMATION: The UPS has returned from a low battery condition |
dupsLoadWarning | 7 | INFORMATION: Loading percent of the UPS over the Load Warning |
|
| value |
dupsNoLongerLoadWarning | 8 | INFORMATION: Returned from Load Warning condition |
dupsLoadSeverity | 9 | Warning: Loading percent of the UPS over the Load Severity value |
dupsNoLongerLoadSeverity | 10 | INFORMATION: Returned from Load Severity condition |
dupsLoadOnBypass | 11 | WARNING: The UPS loads on bypass |
dupsNoLongerLoadOnBypass | 12 | INFORMATION: The UPS is not on bypass mod |
dupsUPSFault | 13 | SEVER: A general fault caused in the UPS |
dupsBatteryGroundFault | 14 | SEVER: The UPS battery ground fault |
dupsNoLongerBatteryFault | 15 | INFORMATION: The UPS recovered from battery ground fault |
dupsTestInProgress | 16 | INFORMATION: The UPS test in progress |
dupsBatteryTestFail | 17 | SEVER: The UPS test in progress |
dupsFuseFailure | 18 | SEVER: The UPS fuse failed |
dupsFuseRecovered | 19 | INFORMATION: The UPS fuse recovered |
dupsOutputOverload | 20 | SEVER: The UPS overload |
dupsNoLongerOverload | 21 | INFORMATION: Recovered from UPS overload |
dupsOutputOverCurrent | 22 | SEVER: The UPS output is over current |
dupsNoLongerOutputOverCurrent | 23 | INFORMATION: Recovered from UPS over current |
dupsInverterAbnormal | 24 | SEVER: The UPS inverter is operating abnormally |
dupsInverterRecovered | 25 | SEVER: Recovered from UPS inverter abnormal state |
dupsRectifierAbnormal | 26 | SEVER: The UPS rectifier is operating abnormally |
dupsRectifierRecovered | 27 | INFORMATION: The UPS recovered from abnormal state |
dupsReserveAbnormal | 28 | SEVER: The UPS rectifier is operating abnormally |
dupsReserveRecovered | 29 | INFORMATION: The UPS rectifier is now operating normally |
dupsLoadOnReserve | 30 | INFORMATION: The UPS load on reserve |
dupsNoLongerLoadOnReserve | 31 | INFORMATION: The UPS no longer load on reserve |
dupsEnvOverTemperature | 32 | WARNING: The environment is over normal temperature |
DupsNoLongerEnvOverTemperatu | 33 | INFORMATION: The environment recovered from abnormal |
re |
| temperatures |