Table 5-2. Electrical Data.

Chapter 5: Performance, Electrical, and Sound Data

Table 5-2. Electrical Data.

 

CRCW-12

 

 

CRCW-24

 

Electrical Data

 

 

 

 

 

 

FLA

MCA

MFS

FLA

MCA

MFS

 

 

 

 

 

 

 

 

Cooling Only

 

 

 

 

 

 

 

 

 

 

 

 

 

120/1/60

9.5

11.9

15

N/A

N/A

N/A

 

 

 

 

 

 

 

208/1/60

5.7

7.1

15

N/A

N/A

N/A

 

 

 

 

 

 

 

208/3/60

5.7

7.1

15

10.0

12.5

15

 

 

 

 

 

 

 

460/3/60

2.8

3.6

15

4.8

6.0

15

 

 

 

 

 

 

 

575/3/60

2.3

2.9

15

3.9

4.9

15s

 

 

 

 

 

 

Cooling and Humidifier

 

 

 

 

 

 

 

 

 

 

 

 

120/1/60

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

208/1/60

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

208/3/60

N/A

N/A

N/A

19.2

24.0

30

 

 

 

 

 

 

 

460/3/60

N/A

N/A

N/A

9.0

11.2

15

 

 

 

 

 

 

 

575/3/60

N/A

N/A

N/A

7.3

9.1

15

 

 

 

 

 

 

 

NOTE: Standard 1 KAIC rating; optional 65 KAIC rating available.

Table 5-3. Sound Data.

Sound Data for CRCW-12

Sound Pressure — LpA, free field (dBA) in a 121.13 ft.2 (3.43 m3) room at 3.28 (1.0 m) distance

 

 

 

 

 

 

 

 

 

 

 

 

Fan Speed %

Airflow (SCFM)

63

125

250

500

1000

2000

4000

8000

Total dBA

NR Value

 

 

 

 

 

 

 

 

 

 

 

 

50%

1800

15.8

19.7

31.3

35.0

38.8

36.1

25.3

10.9

42.0

39

 

 

 

 

 

 

 

 

 

 

 

 

75%

2150

13.1

41.6

42.7

45.2

48.1

46.2

38.5

23.4

52.6

48

 

 

 

 

 

 

 

 

 

 

 

 

100%

2900

19.6

47.2

49.8

51.4

53.6

51.7

45.0

30.6

58.4

54

 

 

Sound Data for CRCW-24

Sound Pressure — LpA, free field (dBA) in a 146.91 ft.2 (4.16 m3) room at 3.28 (1.0 m) distance

 

 

 

 

 

 

 

 

 

 

 

 

Fan Speed %

Airflow (SCFM)

63

125

250

500

1000

2000

4000

8000

Total dBA

NR Value

 

 

 

 

 

 

 

 

 

 

 

 

50%

4100

29.4

42.5

46.6

48.6

52.3

52.5

41.5

26.1

57.0

54

 

 

 

 

 

 

 

 

 

 

 

 

75%

5000

34.9

49.7

57.3

59.7

62.8

60.5

56.0

40.3

67.0

63

 

 

 

 

 

 

 

 

 

 

 

 

100%

5800

43.0

52.6

61.5

64.0

67.0

64.2

59.6

45.8

71.1

67

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All sound testing is performed in accordance with ISO 9614-2 Determination of Sound Power Levels. ISO 9614-2 specifies a method for measuring the component of sound intensity that is normal to a measurement surface. The measurement surface is chosen to enclose the noise source(s) so that the sound power level can be determined.