6 720 608 263
Installation instructions
21
3.8 Measuring gas pressure
Confirm proper gas pressure upon installation.
Connecting Manometer
BShut off gas supply at installer supplied shutoff valve.
BRemove front cover and locate inlet gas pressure
measuring point (see Fig. 24).
BLoosen screw inside left test point fitting (do not
remove) and connect manometer tube to test point.
Remove screw completely if correct size adapter is
available.
Static Pressure Test
BTurn gas supply back on.
BOperate all other gas appliances (except heater) on
same gas piping system at maximum output.
BRecord static gas pressure reading in table 7.
Operating Pressure Test
BON/OFF switch in position OFF (0).
BPress and hold "Program" (P) button and turn ON/
OFF switch to ON position.
Fig. 23
BAs soon as '188' is displayed, release "Program"
, button and the display should read P2.
BPress until P1 appears.
Note: While in this mode the appliance will run
constantly at maximum power and allow maximum water
flow.
BTurn on a high volume of hot water (at least 4 gpm)
and heater will ignite. If heater display reverts to P2,
open more hot water fixtures to allow sufficient flow.
Press until P1 reappears on display.
BRecord lowest operating gas pressure reading in
table 7.
Gas pressures lower than 5" W.C. for Natural Gas or
11" W.C. for LPG will result in insufficient degree rise
to the hot water being used, possible error code faults
and must be corrected. See Gas Connections,
chapter 3.7.
Fig. 24 Gas pressure measuring (left tapping)
HIGH ALTITUDE OPERATION
Static Gas Pressure Reading (see Chapter3.8)
enter here: ___________________ Date: ___________
Operating Gas Pressure Reading (see Chapter 3.8)
enter here: ___________________ Date: ___________
Table 7
Altitude Natural
Gas:
Liquid
Propane:
0 - 4,000 ft
(0 - 1,219 m)
no
modification
no
modification
For operation at
elevations
above 2,000 ft
(610 m) the
equipment
ratings shall be
reduced at the
rate of 4% for
each 1,000 ft
(305 m) above
sea level
4,000 ft - 7,000 ft
(1,219 m - 2,134 m)
CO2 adjustment with flue
gas analyzer required See
section5.4 for instructions.
Above 7,000 ft
(above 2,134 m) Not approved
Table 8