Conettix C900V2 Installation Guide 7.0 UL Standard 864 for Fire System Installations

7.0 UL Standard 864 for Fire System Installations

To install the C900V2 in compliance with UL 864 for Fire System Installations, you must satisfy all requirements in this section. You must install the system in accordance with NFPA-72.

If the control panels are used for fire applications, test according to NFPA-72.

For UL Listed Fire Installations, shared on-premises communications equipment must be UL Listed for Information Technology Equipment.

Installation at the Protected Premises

1.Use the D6200 Software to set the poll rate on the C900V2. For UL approved installations, the maximum interval is 90 seconds to meet the requirement for polling supervision established by UL. In most cases, to get a polling supervision interval of 90 seconds, set the Poll Rate to 75 and Retry to 13.

(For non-UL approved installations, the maximum interval is 300 seconds to meet the requirement for polling supervision set by NFPA Standard 72, Section 5-5.4.4.1. To get a polling supervision interval of 300 seconds, set the Poll Rate to 240 and Retry to 13.)

Because of differences in packet transmission time latency within different networks, the poll rate times vary. Contact Technical Support at Bosch Security Systems, Inc. for help in establishing the latency time for the network on which you are installing the C900V2.

Refer to D6200 Software Operation and Installation Guide (P/N: 4998154991).

2.Set DIP Switch 7 to the OFF position to enable 75-second supervision signals.

Refer to Table 5 on page 10 for the functions of DIP Switches 5 through 9.

3.Add a telnet password to the communications protocol of the C900V2 (refer to Section 4.5.3 Configuration Using Telnet, step 6, on page 16). Retain the password for future reference.

4.Program the control panel to send a daily test signal through the digital dialer.

This tests the connection from the control panel to the C900V2.

5.Connect Output 1 from the C900V2 to a 24-hour zone on the control panel.

This enables the control panel to annunciate a C900V2 CPU failure locally.

6.Connect Output 2 from the C900V2 to a 24-hour zone on the control panel.

This enables the control panel to annunciate a network failure locally.

You must use the C900V2 with a UL Listed Fire Alarm Control Unit or a UL Listed combination Fire/Burglary Alarm Control Unit with an integral or UL Listed digital alarm communicator transmitter (DACT). Refer to the C900TTL-E and C900V2 Compatibility Chart

(P/N: 4998141056).

7.If the C900V2 is installed in a separate enclosure, you must locate the unit in the same room within 6.1 m (20 ft) because the control equipment and the wiring must be enclosed in conduit (or equivalently protected against mechanical injury).

Mounting a C900V2 in a control panel enclosure is approved by UL only when used with a DS 7400Xi as shown in Figure 5 on page 6.

8.You must use the C900V2 with a UL Listed Power Supply (such as Altronix® AL300- ULXR).

9.Set DIP Switch 5 to OFF to disable Auto Fallback.

10.Set DIP Switch 6 to ON to prevent fallback caused hang-ups.

Intercept errors are reported to the receiver. If the receiver does not acknowledge a signal sent that was intercepted by the C900V2 in the programmed time, the control panel digital dialer hangs up and retries the message transmission.

11.Set DIP Switch 9 to ON to enable Anti- Substitution/Anti-Replay.

12.Set the shorting link on P3 to the H position. Refer to Figure 13 on page 24 and Table 11 on page 25 for the proper connection sequence.