6 | en Door Profile | Access Control Interface Module |
|
|
|
Blank Only the area assigned to the D# Entry Area will disarm for this door.
D# Door Point
Default:Blank
Selections: | Blank, |
|
|
Enter the point number that will be assigned to this door. This point cannot be used for any other point assignments.
NOTICE!
Door Points must be programmed as Perimeter Points. If a 24 hour point type is required for the Door Point, you may use a Perimeter Point Type with a Point Response of 9 - C. Also, the Debounce Count must be set to 4 in Point Assignments.
Blank There is no point number assigned to this door.
NOTICE!
When assigning points 1to 8 (panel zones), the end of line resistors must be removed from the panel
NOTICE!
Do not enable any POPIT points (or OctoPOPIT points) sharing the same point number as the Door Point. Failure to do so will result in Extra Point trouble conditions upon reboot.
D# Interlock Point
Default:Blank
Selections: | Blank, |
|
|
Enter the interlock point number. This point, when faulted, will prevent the door controller from allowing access upon a valid ID read or door request.
Do not assign this point as a door point to another door point. You may assign it to another controller thereby having one interlock point prevent multiple controllers from activating.
Blank There is no point number assigned to this door.
NOTICE!
The interlock point will be considered in a normal state if it is bypassed swinger bypassed or forced armed. This will result in normal operation of access even if the door is left open.
F.01U.201.526 02 2011.10 | Program Entry Guide | Bosch Security Systems, Inc. |