Bosch Appliances D9210C manual Strike Profile, # Strike Time, # Shunt Time, # Buzz Time

Models: D9210C

1 18
Download 18 pages 39.32 Kb
Page 9
Image 9

Access Control Interface ModuleStrike Profile en 9

3

Strike Profile

This programming category is used to create a specific door profile on:

Strike and shunt times.

Extending strike and shunt times if a door is left open.

Resetting the strike when the door opens.

Programming the interlock point.

Door #

Default:1

Selections1-8

Enter the door you are programming.

D# Strike Time

Default:10

Selections:

1-240 seconds

 

 

Enter the amount of time the relay output for the strike will activate to allow a user to open the door. The strike will activate upon a valid token, Request to Enter [RTE], Request to Exit [REX], and the Command Center [CYCLE DOOR?] function.

Blank Strike Time is not programmed for this door.

1-240The strike will activate for the amount of time programmed.

D# Shunt Time

Default:10

Selections:

Blank, 1-240

 

 

Enter the amount of time that the door point will be shunted to allow a user to open the door without causing the point to go into Trouble, Alarm or a faulted condition.

Blank TShunt Time is not programmed for this door.

1-240The shunt will activate for the amount of time programmed.

D# Buzz Time

Default:2

Selections:

Blank, 1-240 seconds

 

 

Enter the amount of time that the buzzer output will activate to notify the user that the strike has been activated and the door is ready to open. The buzzer will stop as soon as the door is opened.

NOTICE!

A separate buzzer is required. Many readers have an internal buzzer that is not affected by Buzz Time.

Bosch Security Systems, Inc.

Program Entry Guide

F.01U.201.526 02 2011.10

Page 9
Image 9
Bosch Appliances D9210C manual Strike Profile, # Strike Time, # Shunt Time, # Buzz Time