DS9400M AddressiFire Fire Alarm Control Panel

The DS9400M AddressiFire 255 is a microprocessor-based Fire Alarm Control Panel. This four conventional point panel can expand to 255 input points. It supports up to twenty two-wire detectors per on-board conventional point, or any number of four-wire detectors (depending on available power). Two Notification Appliance Circuits (NACs) provide up to 4 A of 24 V power to operate horns, strobes, bells and other notification appliances. The DS9431 Multiplex Expansion Module (pre-installed) enhances the DS9400M’s conventional system features by adding addressable point capability, increasing the number of relay outputs and allowing for more system users.

Functions

Easy user interface

Nine labeled function keys allow the user to easily silence bells, sirens, reset smoke detectors, or view history events. Menu driven keypad programming allows for customizing of the control panel.

Keypad programmable

The system is completely keypad programmable, thus eliminating the need for an expensive hand-held programmer.

Digital Fire Alarm Control Panel

Provided with four conventional on-board inputs, expandable to eight
Up to 247 Addressable Multiplex Points
Supports two-wire and four-wire conventional type detectors

Two NACs

Two On-Board Auxiliary Relays

Internal 24 V, 4 A power supply

Supports four remote LCD Keypads

On-board programming via front panel

Expandable to 255 points

Initiating circuits

All on-board conventional input points will work with two- wire or four-wire smoke detectors. Twenty detectors (two- wire) maximum per zone.

Multiplex expansion technology

The DS9431 Multiplex Expansion Module (pre-installed) enhances the DS9400M conventional system features by expanding the base system to 255 total points, increasing the number of relay outputs to 58 and adding an additional 400 events to the history buffer for a total of 500 non- volatile events. The DS9431 also allows for up to 100 system users on the DS9400M.

Built-In and remote alpha keypad support

The keypad built in to the control panel and the DS9447 remote LCD keypad are alphanumeric keypads that provide a two-line, 16character (per line) LCD display. Text is freely programmable for zone descriptions. Up to four DS9447 remote LCD keypads are allowed per system.

Personal ID Numbers (PINs)

The system supports up to 100 Personal ID Numbers (PINs), which are four digits in length. The PINs may contain any combination of digits. PINs may be programmed with four different levels of authority. These PINs may be restricted to silencing, resetting, disabling, and/or programming the system.