18 en | Installing the Power Supply Box AutoDome Power Supply Boxes
F.01U.250.895 | 1.0 | 2011.08 Installation Guide Bosch Security Systems, Inc.
2.4 Route Wires and At tach ConnectorsPower wires must be routed to the left (front) side of the
power supply box through a separate conduit. All video,
control, and alarm wires must be routed through a second
conduit to the right side of the box. Refer to Section 3 Cable and
Wire Standards, page 24 for methods of transmitting video and
data, and for wire specifications.
2.4.1 Methods for Routing Wires
There are two possible methods to route the video, control, and
alarm wires:
– One is to route the video, control, and alarm wires through
the conduit fitting on the right (front) side of the power
supply box and out to the AutoDome Arm Mount or to the
Interface Board (for Pipe and Roof Parapet mounts).
WARNING!
External interconnecting cables are to be installed in
accordance to NEC, ANSI/NFPA70 (for US application) and
Canadian Electrical Code, Part I, CSA C22.1 (for CAN
application) and in accordance to local country codes for all
other countries.
Branch circuit protection incorporating a 20 A, 2-pole Listed
Circuit Breaker or Branch Rated Fuses are required as part of
the building installation. A readily accessible 2-pole disconnect
device with a contact separation of at least 3 mm must be
incorporated.