Bradford-White Corp 9kW, 900kW Never turn on the electric, Jacket Assembly, Standard Equipment

Models: 9kW 900kW Commercial Electric Water Heaters

1 28
Download 28 pages 6.99 Kb
Page 10
Image 10
Never turn on the electric

initial operation. Operation of a water heater without a completely filled tank may result in serious damage to the appliance and heating element burn out.

5.The water heater should be connected with a separate grounded branch circuit with over current protection and disconnect switch. The water heater should be grounded in accordance with national and local codes. A ground terminal is provided for ground connection only.

6.Provide the appliance with proper overload protection in the branch circuit. It is suggested that the electrician size the branch circuit at 125 percent of the heater ampere rating and further increase wire size as necessary to compensate for voltage drop in long runs. Branch circuit voltage drop should not exceed 3% at the heater.

7.Voltage applied to the heater should not vary more than +5% to -10% of the model and rating plate marking for satisfactory operation.

8.A wiring diagram is provided with the water heater for the electricians use.

 

CAUTION:

Never turn on the electric

 

 

 

power or attempt to use this electric water heater unless it is completely full of water. Water must flow from the hot water faucet before turning electrical power “ON.” Operation of a water heater without a completely filled tank may result in serious damage to the appliance and heating element burn out

JACKET ASSEMBLY

Outer Jacket – The outer jacket assembly is constructed from steel, galvanized on both sides. The galvanized surface is specially prepared and phosphate coated to allow application of a multiple coat enamel paint process. This coating process insures a long life from the jacket assembly.

STANDARD EQUIPMENT

Your commercial electric water heater is equipped with the following as standard equipment.

Low watt density immersion heating elements with an incoloy sheath.

• Internal fusing of all elements in a maximum of 48 amp increments provides additional safety. Fuse cartridges are related at 1,000,000 amps interrupting capacity.

A galvanized steel outer jacket and electrical control panel are provided.

Channel iron skid base.

Electrical control panel is provided with a hinged door and key lock.

A glass lined steel tank constructed to ASME specifications and provided with magnesium anode(s).

ASME rated temperature and pressure relief valve provided by factory to insure safe heater operation.

Terminal block connections are installed by the factory for safe easy wiring connection.

Manual reset high water temperature limit control.

Immersion thermostat (one per 54kW of input as standard).

180˚F (82.2˚C) temperature operation is possible to provide water for sanitizing applications.

Insulated to meet the latest edition of ASHRAE 90.1 energy efficiency standards.

3 year limited warranty provides protection against failure of tanks due to defects in material and workmanship in commercial application.

Underwriter’s Laboratories, Inc. listing for all models as a commercial electric water heater.