DISPLAY
Once power is applied to the temperature controller the display will countdown from 210 until the display reads zero. All outputs are
SETUP OF THE TEMPERATURE
CONTROLLER
Each stage on the controller has its own independent set point and differential which are determined by the programming keys. Each stage of heating is
EXAMPLE:
Using stage one of the control as an example, the corresponding load would be energized and
Settings
Set point: 160o F
Differential: 8o F
Output Energized
Stage One: Energized at 152o F
Output
Stage One:
Each available stage of operation must be programmed with a set point and a differential. If two stages are programmed with the same set
point and differential the control will sequence both stages on and off with only a slight delay between switching of the stages. The control is normally programmed with a few degrees difference between the set point of each stage to sequence individual stages on as required by demand. This will allow input to be balanced to system demand. The exact settings will be determined by your system hot water requirements.
Based on your system requirements, determine the set point and switching differential for each stage of operation and enter into the worksheet below.
Programming Worksheet
Stage 1: |
|
Set Point 1 ___________ | Off at ___________ |
Differential 1 ________ | On at __________ |
Stage 2: |
|
Set Point 2 ___________ | Off at ___________ |
Differential 2 ________ | On at __________ |
Stage 3: |
|
Set Point 3 ___________ | Off at __________ |
Differential 3 ________ | On at _________ |
Stage 4: |
|
Set Point 4 ___________ | Off at __________ |
Differential 4 ________ | On at _________ |
These values will be programmed into the temperature controller.
16