D A N G E R
TEMPERATURE ADJUSTMENT
HOT!
BURN
FIG. 18
•Water temperature over 125˚F can cause severe burns instantly or death from scalds.
•Children, disabled and elderly are at highest risk of being scalded.
•See instruction manual before setting temperature at heating appliance.
•If this appliance is used to produce water that could scald if too hot, such as domestic hot water use, adjust the outlet control (limit) or use temperature limiting valves to obtain a maximum water temperature of 125˚F. SEE MANUAL.
1. | Turn “OFF” the electrical power to the water | |
| heater. If the power disconnect point is out of | |
| sight, lock it in the open (“OFF”) position | |
| and tag to prevent unexpected application | |
| of power. |
|
2. | Open the water heater’s electrical access panel. | |
3. | Adjust each immersion thermostat to | the |
| desired temperature setting by turning | the |
WARNING:
WARNING: SHOULD OVERHEATING OCCUR OR THE TEMPERATURE CONTROLS FAILTO SHUT OFF,TURN OFF OR DISCONNECT THE ELECTRICAL SUPPLY AT THE MAIN POWER DISCONNECT EXTERNAL TO THE APPLIANCE.
DANGER:
•Water temperature over 125˚ F (51.7°C) can cause severe burns instantly or death from scalding.
•Children, disabled and elderly are at highest risk of being scalded.
•See instruction manual before setting temperature at heating appliance.
•Feel water before bathing or showering.
•If this appliance is used to produce water that could scald if too hot, such as domestic hot water use, adjust the outlet control (limit) or use temperature limiting valves to obtain a maximum water temperature of 125˚ F (51.7° C).
Always close the electrical control panel door after making a temperature adjustment. Turn on electricity.
| adjusting knob. Each thermostat will be |
| factory |
| (51.7° C) or less as shipped. |
4. | Close the water heater’s electrical access panel. |
5. | Turn “ON” the electrical power to the |
| water heater. |
CAUTION: | The maximum temperature |
|
|
setpoint that should be set for the Immersion Thermostats or programmed into the Electronic Temperature Control Sequencer is 190° F ( 88° C)
ELECTRONIC TEMPERATURE
CONTROL SEQUENCER
FIG. 19 Electronic Temperature Control with Digital Display
14