Bradford-White Corp 50T65F, CX), MI50L SERVICE PROCEDURE RG-VIII ScreenLok Flame Arrestor Cleaning

Models: M4403S M1XR403S*FCX M4403T MI60T MI30S MI403S M2C504T MI503 50T65F M460T MI40T M1XR504T M4503 M440T MI303T MI504S M1XR403S*FBN M450S M430T MI30T MI404T CX) M2XR504T MI50L

1 28
Download 28 pages 24.42 Kb
Page 22
Image 22
SERVICE PROCEDURE RG-VIII

SERVICE PROCEDURE RG-VIII

ScreenLok® Flame Arrestor Cleaning

ScreenLok® Flame Arrestor Cleaning

Step 1. Rotate knob of combination thermostat gas valve to the off position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

Step 2. Remove outer jacket door.

Step 3. Remove inner door per SERVICE PROCEDURE RG-I, step 3a through 3e.

Step 4. Disconnect main burner feed line (¾ wrench), pilot tube (7/16 wrench) and thermocouple (3/8) wrench from combination thermostat gas valve and remove burner assembly from combustion chamber.

NOTE: Feedline nut for natural gas control uses right hand threads, LP control uses left hand thread.

Feedline

Nut

Step 5. Clean ScreenLok® Flame Arrestor using stiff brush, compressed air and/or shop vacuum to remove any scale or other debris accumulation. Using a soft brush, clear jacket openings of any dirt, dust, restrictions or other obstructions.

Step 6. Remove any debris from burner assembly per SERVICE PROCEDURE RG-V and reinstall burner assembly into combustion chamber.

Step 7. Reconnect feedline, thermocouple and pilot tube to the combination thermostat/gas valve. Step 8 Reinstall inner door per SERVICE PROCEDURE RG-I, steps 4 through 13.

Step 9. To resume operation follow the instructions located on the lighting instruction label or the lighting instruction located in the installation and operation manual.

23

Page 22
Image 22
Bradford-White Corp 50T65F, CX), M1XR403S*FCX, MI50L, MI504S SERVICE PROCEDURE RG-VIII ScreenLok Flame Arrestor Cleaning