INSTALLATION

 

 

 

 

 

 

 

 

 

 

Temperature/Pressure Relief Valves

Pressure Reducing Valve

For protection against excessive pressures and temperatures in

 

 

 

the booster heater, install temperature/pressure protective

 

CAUTION

 

equipment required by local codes. The temperature/pressure

 

 

If water supply pressure to the booster water heater inlet

relief valve supplied with this booster water heater is

constructed with brass working parts and heat resistant silicone

is over 20 psi (138 kPa) during flow, install a commercial-

seat discs.

grade pressure reducing valve with built-in bypass for

proper operation of dish machine rinse nozzles.

 

 

 

 

 

WARNING

 

NOTE: The pressure reducing valve must be the type

Temperature/pressure

 

protective equipment should not be

equipped with a high pressure bypass like the valve

 

less than a combination temperature/pressure relief valve

supplied with this booster water heater.

certified by a nationally recognized testing laboratory that

Proper operation of the commercial dish machine rinse nozzles

maintains periodic inspection of the production of this

requires that available water pressure at the rinse nozzle be

equipment and meets the requirements for Relief Valves

between 15 and 25 psi (103 and 172 kPa) when the nozzle is

and Automatic Shutoff Devices for Hot Water Supply

operated. 20 psi (138 kPa) is recommended. If water pressure

Systems, ANSI Z21.22-1979. The temperature/pressure

available to the booster water heater inlet is over 20 psi

relief valve must be marked with a minimum set pressure

(138 kPa), a pressure reducing valve must be installed in the hot

not to exceed the marked hydrostatic test pressure of the

water supply line to the booster water heater and adjusted to

booster heater as noted on the unit specifications.

deliver 20 psi (138 kPa) flow pressure.

FOR INSTALLING COMBINATION TEMPERATURE/

The valve supplied with the unit has a built-in high pressure

PRESSURE RELIEF VALVES IN ACCORDANCE WITH

bypass that prevents excessive pressure build-up as the

AMERICAN NATIONAL STD. Z21.22-1979. Combination

booster heats up. Final adjustment is required at the time of

temperature/pressure relief valves with extension

installation.

thermostats must be installed so that the temperature-

Temperature/Pressure Gauges

sensing element is immersed in the water within the top 6"

(152 mm) of the tank. They must be installed either in the

 

 

 

hot outlet service line or directly in a tank tapping.

 

CAUTION

 

Combination temperature/pressure relief valves that do

 

 

Bradford White requires that two temperature/pressure

not have extension elements must be mounted directly in

a tank tapping located within the top 6" (152 mm) of the

gauges be installed to assure proper operation. Install one

tank, and shall be adequately insulated and located so as

in the supply line before the pressure reducing valve and

to assure isolation from the flue gas heat or other ambient

one in the outlet line as close to the booster water heater

conditions that are not indicative of stored water

as possible. This provides a visual check of the water

temperature. TO AVOID WATER DAMAGE OR SCALDING

temperature and pressure before and after the water

DUE TO VALVE OPERATION, DRAIN PIPE MUST BE

heater.

CONNECTED TO VALVE OUTLET AND RUN TO A SAFE

NOTE: If a check valve is installed and cannot be removed

PLACE OF DISPOSAL. Discharge line must be as short as

install a back pressure relief valve set at 125 psi (862

possible and be the same size as the valve discharge

kPa) on the incoming line between the pressure

connection throughout its entire length. Drain line must

reducing valve and the inlet to the booster water

pitch downward from the valve and must terminate

heater. Discharge must be to open site drain (see

between 1-1/2" (38 mm) and 6" (152 mm) above the floor

Figure 7).

drain where any discharge will be clearly visible. The drain

line shall terminate plain, not threaded, with material

Blended Phosphate Water Treatment

greater. Excessive length, over 30' (9144 mm), or use of

System (optional)

serviceable for temperatures up to 250°F (121°C) or

Bradford White recommends that the Blended Phosphate Water

more than four elbows can cause a restriction and reduce

the discharge capacity of the valve. No shut-off valve shall

Treatment System be installed with unions on the incoming 3/4"

be installed between the relief valve and tank, or in the

water supply line after the pressure reducing valve and before

drain line. Valve lever must be tripped periodically to

the booster water heater.

assure that waterways are clear. This device is designated

Cartridges supplied have a usage rating of 100,000 gallons

for emergency safety relief and shall not be used as an

(378,541 liters) of water. To assure proper operation the

operating control. The valves are set to relieve at 150 psi

cartridges must be replaced when expired.

(1034 kPa) or when water temperature reaches 210°F

NOTE: Product failure caused by liming or sediment buildup is

(99°C). Read tag on valve for additional information.

 

 

 

 

 

 

 

not covered under warranty.

 

 

 

 

 

CAUTION

 

 

 

 

BURN HAZARD: Valves supplied with

this booster water

 

 

 

heater are designed for high temperature commercial

 

 

 

operation. Do not substitute these valves with valves

 

 

 

designed for domestic water heaters.

 

 

 

Do

not use an anti-siphon or check valves on incoming

 

 

 

water line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

Form No. EBOOSTERBWM-1009

Page 10
Image 10
Bradford-White Corp 07.05.228.00 Temperature/Pressure Relief Valves Pressure Reducing Valve, Temperature/Pressure Gauges