Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER operation manual

Models: 238-47707-00E REV 7/12 POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER

1 60
Download 60 pages 18.66 Kb
Page 13
Image 13

Figure 3.

Direct Vent Terminal Clearances

 

 

Canadian Installations1

US Installations2

A=

Clearance above grade, veranda, porch, deck or balcony

12 inches (30 cm)

12 inches (30 cm)

 

 

 

 

B=

Clearance to widow or door that may be opened

36 inches (91 cm)

12 inches (30 cm)

 

 

 

 

C=

Clearance to permanently closed widow

*b

*b

 

 

 

 

D=

Vertical clearance to ventilated soffit located above the terminal within a

12 inches (30 cm) *a

12 inches (30 cm) *a

horizontal distance of 2 feet (61 cm) from the center line of the terminal

 

 

 

E=

Clearance to unventilated soffit

12 inches (30 cm) *a

12 inches (30 cm) *a

 

 

 

 

F=

Clearance to outside corner

*b

*b

 

 

 

 

G=

Clearance to inside corner

*b

*b

 

 

 

 

 

 

3 feet (91 cm) within a

 

H=

Clearance to each side of center line extended above meter/regulator

height 15 feet (4.6 m)

*b

assembly

above the meter/regulator

 

 

 

 

assembly

 

I=

Clearance to service regulator vent outlet or oil tank vent

36 inches (91 cm)

*b

 

 

 

 

J=

Clearance to non-mechanical air supply inlet to building or the combustion air

36 inches (91 cm)

12 inches (30 cm)

inlet to any other appliance

 

 

 

K=

Clearance to a mechanical air supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if

within 10 feet horizontally

 

 

 

L=

Clearance above paved sidewalk or paved driveway located on public

7 feet (2.13 m)†

*b

property

 

 

 

M=

Clearance under a veranda, porch, deck, or balcony

12 inches (30 cm) ‡

12 inches (30 cm) ‡

1In accordance with the current CAN/CGA-B149 Installation Codes.

2In accordance with the current ANSI Z223.1-(Latest edition)/NFPA 54 National Fuel Gas Code.

† A vent must not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings.

Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. *a) A minimum clearance value determined by testing in accordance with section 2.20.

*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.

13

Page 13
Image 13
Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Direct Vent Terminal Clearances