B.HORIZONTALLY THROUGH WALL (refer to Figure 9)

8

INSTALLATION

B.HORIZONTALLY THROUGH WALL (refer to Figure 9)

NOTE: Follow L-Vent chimney manufacturer’s instructions.

1.Position stove, adhering to clearances shown in Figures 1 & 2.

2.Locate position of hole in wall; directly behind stove exhaust vent (refer to figure 5).

3.Always maintain 3” clearance from combustible materials.

4.Install L-Vent wall thimble per L-Vent manufacturer’s instructions.

5.Attach enough piping to penetrate and extend at least 6” beyond exterior walls. A minimum 8-foot vertical pipe run is suggested where possible to reduce the possibility of smoke spillage in the event of a loss of negative pressure.

6.Attach cap and seal outside wall thimbles with non-hardening waterproof mastic.

7.Termination should not be located so that hot exhaust gases can ignite trees, shrubs, or grasses or be a hazard to children. Exhaust gases can reach temperatures of 500ºF and

cause serious burns if touched.

FIGURE 9

Locate terminations: a) not less than 3 feet above any forced air inlet located within 10 feet; b) not less than 4 feet below or horizontally from, or one foot above, any door, window or gravity air inlet into any building; c) not less than two feet from an adjacent building and not less than 7 feet above grade when located adjacent to a public walkway. Mobile home installations must use a spark arrester.

Page 8
Image 8
Breckwell P23FSL, P23I, P23FSA owner manual Installation, B.HORIZONTALLY THROUGH WALL refer to Figure

FAQ

What are the clearances required for installation?

The clearances for installation can be found in Figures 1 & 2 of the manual. Always maintain a 3-foot clearance from combustible materials.

How should the terminations be located for safety?

Terminations should be not less than 3 feet above any forced air inlet, not less than 4 feet below or horizontally from any door, window or gravity air inlet, and not less than 2 feet from an adjacent building. For mobile home installations, a spark arrester must be used.

What should be used to seal the outside wall thimbles?

Install L-Vent wall thimble per L-Vent manufacturers instructions and seal outside wall thimbles with non-hardening waterproof mastic.