INSTALLATION
B.HORIZONTALLY THROUGH WALL (refer to Figure 9)
NOTE: Follow
1.Position stove, adhering to clearances shown in Figures 1 & 2.
2.Locate position of hole in wall; directly behind stove exhaust vent (refer to figure 5).
3.Always maintain 3” clearance from combustible materials.
4.Install
5.Attach enough piping to penetrate and extend at least 6” beyond exterior walls. A minimum
6.Attach cap and seal outside wall thimbles with
7.Termination should not be located so that hot exhaust gases can ignite trees, shrubs, or grasses or be a hazard to children. Exhaust gases can reach temperatures of 500ºF and
cause serious burns if touched. | FIGURE 9 |
Locate terminations: a) not less than 3 feet above any forced air inlet located within 10 feet; b) not less than 4 feet below or horizontally from, or one foot above, any door, window or gravity air inlet into any building; c) not less than two feet from an adjacent building and not less than 7 feet above grade when located adjacent to a public walkway. Mobile home installations must use a spark arrester.