C. VERTICALLY INTO EXISTING CHIMNEY SYSTEM

INSTALLATION

B.VERTICALLY WITH NEW CHIMNEY SYSTEM (Refer to Figure 10)

NOTE: Follow L-Vent chimney manufacturer’s instructions.

OPTION: To achieve a center vertical installation a 45º elbow and a clean-out tee can be used to offset the pipe from the exhaust outlet to the rear center of the stove.

OPTION: Install L-Vent elbow in place of clean-out tee. Locate stove. Drop plumb bob to center of tee outlet, mark point on ceiling. Install ceiling support and L-Vent pipe per L-Vent manufacturer’s instructions.

1.Always maintain 3” clearance from combustible materials. When passing through additional floors or ceilings, always install firestop spacer.

2.After lining up for hole in roof, cut either around or square hole in roof, always 3” larger all the way around pipe. Install upper edge and sides of flashing under roofing materials, nail to the roof along upper edge. Do not nail lower edge. Seal nail heads with non-hardening waterproof mastic.

3.Apply non-hardening, waterproof mastic where the storm collar will meet the vent and flashing. Slide storm collar down until it sits on the flashing. Seal and install cap. Mobile home installations must use a spark arrester.

C. VERTICALLY INTO EXISTING CHIMNEY SYSTEM

FIGURE 10

 

 

Adapters are available to adapt from 3” L-Vent to 6” or 8” Class-A chimney. (Figure 11a)

As an alternative, 3” or 4” L-Vent can be run inside existing chimney to termination. (Figure 11b)

This is the preferred method.

Follow guidelines for equivalent vent length.

FIGURE 11a

FIGURE 11b

9

Page 9
Image 9
Breckwell P23I, P23FSA, P23FSL owner manual Installation, a b, C. Vertically Into Existing Chimney System

FAQ

Can I install the fireplace vertically with a new chimney system?

Yes, you can install the fireplace vertically with a new chimney system. Refer to Figure 10 and follow the L-Vent chimney manufacturer's instructions for proper installation.

What are the options for achieving a center vertical installation?

To achieve a center vertical installation, you can use a 45 elbow and a clean-out tee to offset the pipe from the exhaust outlet to the rear center of the stove. Alternatively, you can install an L-Vent elbow in place of the clean-out tee.

How should I install the L-Vent pipe per manufacturer's instructions?

To install the L-Vent pipe, locate the stove, drop a plumb bob to the center of the tee outlet and mark a point on the ceiling. Then, install the ceiling support and L-Vent pipe per the L-Vent manufacturer's instructions.