Briggs & Stratton Power Products Home Generator System

Owners Manual

A switch on the control panel is labeled “Set Exercise” (depicted on page 10).The specific day and the specific time of day this switch is pressed is programmed into the control board memory.This date and time is then used to automatically initiate the system exercise cycle.

To perform the Set Exercise procedure:

1.Choose the day and time you want your Home Generator System to exercise.

2.On that day and time, set the AUTO/OFF/MANUAL switch to OFF.

3.Press and hold down the “Set Exercise” switch until the Diagnostic LED turns on (about five seconds).

4.Hold the switch down until the Diagnostic LED turns off. Release the Set Exercise switch.

5.Set the AUTO/OFF/MANUAL switch to AUTO. “Set Exercise” is complete.

For example, if you press the “Set Exercise” switch on Sunday morning at 10:00 AM, the unit will run an exercise cycle the following Sunday at 10:00 AM.

NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed.The exerciser does not need to be re-set if the 15 Amp fuse is removed or changed.The exerciser will need to be re-set if the 12 Volt DC battery is disconnected.

If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.

SPECIFICATIONS

Generator

Model . . . . . . . . . . . . . . . . . . . . 01679-0

Rated Maximum Power (LP*). . . 10.0 kW

Rated Maximum Load Current:

at 240 Volts . . . . . . . . . . . . . . . 41.7 Amps

at 120 Volts . . . . . . . . . . . . . . . 83.3 Amps

Rated AC Voltage . . . . . . . . . . . . 120/240 Volts Rated Frequency . . . . . . . . . . . . 60 Hz at 3600 rpm Phase . . . . . . . . . . . . . . . . . . . . . Single Phase Power Factor . . . . . . . . . . . . . . . 1.0

NG Fuel Supply Pressure. . . . . 5-14 in W.C. (127-356 mm)

LP Fuel Supply Pressure. . . . . . 11-14 in W.C. (279- 356 mm)

Normal Operating Range . . . . -20°F (-28.8°C) to 104°F (40°C)

Output Sound Level . . . . . . . . 70 dB(A) at 23 ft. (7 m) at full load

Shipping Weight . . . . . . . . . . . . 482 lbs.

*Natural gas rating will depend on specific fuel but typical derates are between 10 to 20% off the LP gas rating.

Transfer Switch

Maximum Circuits . . . . . . . . . . . 10

Maximum Load/Circuit:

from Generator . . . . . . . . . . . 41.7 Amps from Load Center. . . . . . . . . . 50 Amps

Maximum Watts . . . . . . . . . . . . . 10,000

15

Page 15
Image 15